Burner adjustment when connecting multiple...
For multiple connection, in the commissioning assis-
tant use "C.5" and "C.6" to match the burner setting
to the flue system. See page 30.
System conditions:
Shared flue in shaft
100 mm
7
Balanced flue connection pipe from boiler to shaft,
80/125 mm
7

Removing the burner

Danger
Contact with live components can lead to seri-
ous injury from electric current. Some compo-
nents on PCBs remain live even after the power
supply has been switched off.
Never touch the wiring chambers (control unit
and power supply connections).
When working on the appliance, isolate the
system from the power supply, e.g. at a sepa-
rate MCB/fuse or a mains isolator. Check the
system is no longer live and safeguard against
reconnection.
Prior to working on the appliance, wait at
least 4 min until the voltage has completely
dropped out.
1. Turn off the ON/OFF switch.
2. Close the gas shut-off valve and safeguard against
reopening.
3. Disconnect cables and leads from:
Fan motor
(2 plugs)
A
Ionisation electrode
Ignition unit
C
Earth
D
B
Commissioning, inspection, maintenance
(cont.)
Minimum shaft cross-section
Square: 175 x 175 mm
Round:
195 mm
7
Height between floors min. 2.5 m
Max. 6 boilers with the same rated heating output
connected to the flue system
4x
F
D
C
B
A
Fig. 28
4. Undo gas supply pipe fitting
5. Undo 4 screws
and remove the burner.
F
Note
Cover gas connection
can fall into it.
E
.
E
so that no small parts
E
41