Burner adjustment when connecting multiple...
For multiple connection, in the commissioning assis-
tant use "C.5" and "C.6" to match the burner setting
to the flue system. See page 30.
System conditions:
Shared flue in shaft
100 mm
■
7
Balanced flue connection pipe from boiler to shaft,
■
80/125 mm
7
Removing the burner
Danger
Contact with live components can lead to seri-
ous injury from electric current. Some compo-
nents on PCBs remain live even after the power
supply has been switched off.
■
Never touch the wiring chambers (control unit
and power supply connections).
■
When working on the appliance, isolate the
system from the power supply, e.g. at a sepa-
rate MCB/fuse or a mains isolator. Check the
system is no longer live and safeguard against
reconnection.
■
Prior to working on the appliance, wait at
least 4 min until the voltage has completely
dropped out.
1. Turn off the ON/OFF switch.
2. Close the gas shut-off valve and safeguard against
reopening.
3. Disconnect cables and leads from:
■
Fan motor
(2 plugs)
A
■
Ionisation electrode
■
Ignition unit
C
■
Earth
D
B
Commissioning, inspection, maintenance
(cont.)
Minimum shaft cross-section
■
–
Square: 175 x 175 mm
–
Round:
195 mm
7
■
Height between floors min. 2.5 m
■
Max. 6 boilers with the same rated heating output
connected to the flue system
4x
F
D
C
B
A
Fig. 28
4. Undo gas supply pipe fitting
5. Undo 4 screws
and remove the burner.
F
Note
Cover gas connection
can fall into it.
E
.
E
so that no small parts
E