Flex Vent
The flex vent must be supported with the spacing between
support intervals not exceeding 4 feet, with no more than ½
inch sag between supports.
A support is required at each change in venting direction,
and in any location where it is necessary to maintain the
necessary clearance to combustibles. A simple "up and out"
installation (Figure 9) requires only enough support to main-
tain the necessary clearance to combustibles. However, the
vent attachment point and the firestop location are consid-
ered to be supports.
3" CLEARANCE
FLEX-VENT
Figure 9.
STRAIGHT OUT HORIZONTAL VENTING
Max. Run
36" (914 mm)
Note: You may use a 45
corner installations for models SL-
550TR-C and SL-750TR-C ONLY.
o
Use two 90
elbows for corner
installations on SL-950TR-C.
Use DVP-Series
components only.
Figure 11. Straight Out Horizontal Venting
TERMINATION
CAP
1"
CLEARANCE
H
o
elbow in
H
STRAIGHT UP
VERTICAL VENTING
V (FT.)
45' MAX.
NOTE: For vertical venting
over 20 feet a restrictor
plate is recommended for
improved flame appearance.
Use SL D-Series
components only.
Figure 10.
Straight up Vertical Venting
For corner installation of models SL-
550TR-C and SL-750TR-C ONLY.
For corner
installation of
model SL-950TR-C.
0
The use of two 90
elbows in a corner
installation will affect space
requirements (see Fig. 4)
20
CAP
45-DEGREE
ELBOW
90-DEGREE
ELBOWS