Twin Pipe Polypropylene And Cpvc Systems - Dunkirk DMG-240 Installation, Operation & Maintenance Manual

Condensing gas fired boiler
Table of Contents

Advertisement

6.6 Twin Pipe Polypropylene and CPVC Systems

Twin pipe venting allows exhaust flue and intake flue to be
separated from each other. Fresh air is drawn in at a different
area from the flue terminal location.
A. Twin Pipe CPVC System
CPVC is approved for boiler exhaust. CPVC or PVC are both
approved for air intake.
To transition from Coaxial at the top of the boiler to Twin Pipe
CPVC/PVC a kit is available.
B. Twin Pipe Polypropylene System
Single wall polypropylene is used for both exhaust and air
intake piping.
To transition from Coaxial at the top of the boiler to Twin Pipe
polypropylene venting an adapter kit is available.
C. Twin Pipe Separated Flue
Exhaust and combustion air intake are not located in same
general location.
D. Twin Pipe - Common Atmospheric Zone Termination
Twin Pipe Maximum Vent Lengths (See Figure 6-4)
Intake Vent
Exhaust Vent
Combined Vent
Elbow
45°
90°
Do not count first elbow against maximum vent
Note
length.
If using indoor air for combustion do not exceed
Note
100ft (30m) exhaust vent pipe.
6 - COMBUSTION AIR AND VENT PIPING
L1
49 ft (15m)
L2
51 ft (15.5m)
L1+L2
100 ft (30.5m)
Total Length Reduction
10" (0.3 m)
2 ft
(0.6 m)
FIGURE 6-3 - Two Pipe Polypropylene System
Adapter
FIGURE 6-4 - Separated Horizontal Flue Termination
23
Boiler
P/N 240011656, Rev. E [07/30/2018]

Advertisement

Table of Contents
loading

Table of Contents