3onedata IMC102B-F User Manual page 3

Industrial ethernet media converter

Advertisement

1.
Check the DIN-Rail attachment
2.
Check DIN Rail whether be firm and the position is
suitability or not.
3.
Insert the top of the DIN-Rail into the slot just below the
stiff metal spring.
4.
The DIN-Rail attachment unit will snap into place as
shown below.
Wiring Requirements
Cable laying need to meet the following requirements,
1. It is needed to check whether the type, quantity and
specification of cable match the requirement before
cable laying;
2. It is needed to check the cable is damaged or not, factory
records and quality assurance booklet before cable
laying;
3. The required cable specification, quantity, direction and
laying position need to match construction requirements,
and cable length depends on actual position;
4. All the cable cannot have break-down and terminal in the
middle;
5. Cables should be straight in the hallways and turning;
6. Cable should be straight in the groove, and cannot
beyond the groove in case of holding back the inlet and
outlet holes. Cables should be banded and fixed when
they are out of the groove;
7. User cable should be separated from the power lines.
Cables, power lines and grounding lines cannot be
overlapped and mixed when they are in the same groove
road. When cable is too long, it cannot hold down other
cable, but structure in the middle of alignment rack;
8. Pigtail cannot be tied and swerved as less as possible.
Swerving radius cannot be too small (small swerving
causes terrible loss of link). Its banding should be
moderate, not too tight, and should be separated from
other cables;
9. It should have corresponding simple signal at both sides
of the cable for maintaining.
【Specification】
Technology
Standard: IEEE802.3, IEEE802.3u, IEEE802.3x
Flow control: IEEE802.3x flow control, back press flow
control
Exchange Attribute
100M forward speed: 148810pps
Transmit mode: store and forward
System exchange bandwidth: 1.6Gbps
MAC address table: 2K
Memory: 1Mbit
Interface
RJ45 port: 10/100Base-T(X) auto speed control, Half/full
duplex and MDI/MDI-X auto detect
Fiber port: 100Base-FX, SC/ST/FC connector
Transfer Distance
Twisted cable: 100M (standard CAT5/CAT5e cable)
Multi-mode: 1310nm, 2Km
Single-mode: 1310nm, 20/40/60Km
1550nm, 80/100/120Km
- 3 -
LED Indicator
Interface indicator: Link (1~3)
Power supply indicator: PWR
DIP Switches
NO.1: Flow Control
NO.2: Force RJ45 to 10M
Power Supply
Input Voltage: 100~240VAC
Type of input: 3 bits7.62mm terminal block
Consumption
No-load consumption: 1.6W@220VAC
Full-load consumption: 2.0W@220VAC
Working environment
Working temperature: -40~167° F (-40~75° C)
Storage temperature: -40~185° F (-40~85° C)
Relative Humidity: 5%~95 %( non-condensing)
Mechanical Structure
Shell: IP40, high strength iron shell.
Installation: DIN-Rail
Dimension (W×H×D): 35mm ×110 mm×95mm
Weight: 340g
Industry Standards
EMI: FCC Part 15, CISPR (EN55022) class A
EMS: IEC 61000-4-2 (ESD), Level 3
IEC 61000-4-4 (EFT), Level 3
IEC 61000-4-5 (Surge), Level 3
Shock: IEC 60068-2-27
Free fall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Warranty
Warranty: 5 years