Accessories - Riello RL 64 MZ Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

ACCESSORIES (optional):
• STATUS (see page 15): code 3010322
RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
BURNER
Code
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a
consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations.
Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
Degassing unit characteristics
• Burner delivery
: 80 kg/h max
• Light oil pressure
: 0.7 bar max
• Ambient temperature
: 40 °C max
• Light oil temperature
: 40 °C max
• Attachment connectors
: 1/4 inch
• CLEAN CONTACT KIT: code 3010419
RL 64 MZ
3010386
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

34704103470411

Table of Contents