Electrical Work - Mitsubishi Electric CITY MULTI PKFY-P VLM Series Installation Manual

Air-conditioners for building application indoor unit
Hide thumbs Also See for CITY MULTI PKFY-P VLM Series:
Table of Contents

Advertisement

Available languages

Available languages

5. Drainage piping work
C

6. Electrical work

Indoor unit side
Secure with a band
N
at the location shown
in the diagram
N
M
A
~220-240V
~220-240V
RH79A015H01_en.indd 9
D
A
B
E
Fig. 5-3
Fig. 5-4
D
G
F
E
A
L
K
JKL
J
55 mm
12 mm
C
G
I
L
E
Fig. 6-1
D
B
C
C
C
C
C
A
B
D
L N
M1
M2
S
1 2
C
TB2
TB5
TB15
Fig. 6-2
Storing in the piping space of the indoor unit (Fig. 5-3)
* When the drain hose will be routed indoors, be sure to wrap it with commercially
available insulation.
* Gather the drain hose and the refrigerant piping together and wrap them with the
supplied felt tape 3.
* Overlap the felt tape 3 at one-half of the tape width.
* Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe
B Liquid pipe
C Drain hose
D Indoor/outdoor connection wiring
E Felt tape 3
Check of drainage (Fig. 5-4)
1. Open the front grille and remove the filter.
2. Facing the fins of the heat exchanger, slowly fill with water.
3. After the drainage check, attach the filter and close the grille.
6.1. Electric wiring
B
[Fig. 6-1]
Connection can be made without removing the front panel.
B
1. Open the front grille, remove the screw (2 pieces), and remove the electrical
parts cover.
* Electrical work can be conducted more effectively with the panel removed.
When attaching the panel, check that the hooks M at three locations on the air
outlet side are connected securely.
2. Securely connect each wire to the terminal block.
* In consideration of servicing, provide extra length for each of the wires.
* Take care when using strand wires, because beards may cause the wiring to
short out.
3. Install the parts that were removed back to their original condition.
4. Fasten each of the wires with the clamp under the electrical parts box.
Electrical box cover
A
Fixing screw
B
C
Clamp
Ground wire connection portion
D
MA remote control terminal block: (1, 2) do not have polarity
E
Transmission terminal block: (M1, M2, S) do not have polarity
F
Power supply terminal block (L, N,
G
H
Terminal screw
Ground wire connection portion: Connect the ground wire in the direction illustrated in the
I
Remote control cable
J
Transmission cable
K
Power supply cable
L
M
Hook
N
Band
Caution:
Wiring for remote controller cable shall be apart (5 cm or more) from power
source wiring so that it is not influenced by electric noise from power source
wiring.
6.2. Power supply wiring
• Wiring size must comply with the applicable local and national codes.
• Power supply cable of appliance shall not be lighter than design 60245 IEC 53 or
60227 IEC57, 60245 IEC 53 or 60227 IEC 53.
• Install a ground wire longer than other cables.
F
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 6-2]
A
Ground-fault interrupter
B
Local switch/Wiring breaker
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
).
diagram.