Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
SMMS-i
(4 series)
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
05: TK5 oil
circuit error
H16
H16
H25
H25
L02
L02
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
Location
Description
System status
of
detection
I/F
Oil level
All stop
detection
circuit error
I/F
TD3 sensor
All stop
miswiring
(incomplete
insertion)
Indoor
Outdoor unit
Only the target
unit
model
unit stopped
mismatch
error
Indoor
Duplicated
Stop of
unit
indoor header
corresponding
unit
unit
I/F
Duplicated
All stop
outdoor line
address
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
indoor unit
other than
priority indoor
unit)
Indoor
Connection of
Stop of
unit
group control
corresponding
cable to stand-
unit
alone indoor
unit
Indoor
Indoor group /
Stop of
unit
addresses not
corresponding
set
unit
Indoor
Indoor
Stop of
unit
capacity not
corresponding
set
unit
- 72 -
Error detection
Check items (locations)
condition(s)
No temperature
Check for disconnection of TK4 sensor.
change is detected
Check resistance characteristics of
by TK4 despite
TK4 sensor.
compressor having
Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
Check for faulty operation in SV3E or
SV3F valve.
Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
Check for refrigerant entrapment inside
compressor.
No temperature
Check for disconnection of TK5 sensor.
change is detected
Check resistance characteristics of
by TK5 despite
TK5 sensor.
compressor having
Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
Check for faulty operation in SV3E
valve.
Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
Check for refrigerant entrapment inside
compressor.
Air discharge
Check installation of TD3 sensor.
temperature (TD3)
Check connection of TD3 sensor
does not increase
connector and wiring.
despite compressor
Check resistance characteristics of
3 being in operation.
TD3 sensor.
Check for defect in outdoor P.C. board
(I/F).
An error was found
Check the model name of the outdoor
on the outdoor unit
unit.
model.
Check the miswiring of the
communication line between indoor
and outdoor.
There is more than
Check indoor addresses.
one header unit in
Check for any change made to remote
group.
controller connection (group /
individual) since indoor address
setting.
There is duplication
Check line addresses.
in line address
setting for outdoor
units belonging to
different refrigerant
piping systems.
More than one
Check display on priority indoor unit.
indoor unit has been
set up as priority
indoor unit.
More than one
Check displays on priority indoor unit
indoor unit have
and outdoor unit.
been set up as
priority indoor unit.
There is at least one
Check indoor addresses.
stand-alone indoor
unit to which group
control cable is
connected.
Address setting has
Check indoor addresses.
not been performed
Note:
for indoor units.
This code is displayed when power
is turned on for the first time after
installation.
Capacity setting has
Set indoor capacity. (DN = 11)
not been performed
for indoor unit.