NO.
Item
Fan speed
1. The fan operates in one of the four speed modes of "HIGH (HH)", "MED
(H)", "LOW (L)" and "AUTO" on the basis of a command issued via the
control
remote controller. (Concealed duct high static pressure type: HH only)
2. In AUTO fan speed mode, the air speed changes according to the
difference between Ta and Ts.
<Cooling>
• Control is identical in remote controller thermo and body thermo
• In AUTO fan speed mode, the fan speed remains the same for 3 minutes
5
• At the beginning of cooling operation, a higher speed (steeper downward
• As long as the temperature difference remains on a boundary line, the
<Heating>
Figures inside ( ) applies to remote controller thermo operation.
Figures outside ( ) applies to body thermo operation.
Speed modes shown in < > apply to heating operation under AUTO air
conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 1 minute
• At the beginning of heating operation, a higher speed (steeper upward
• As long as the temperature difference remains on a boundary line, the
• When TC2 ≥ 60 °C, the fan speed is raised by one step.
3. If the air conditioner goes thermo OFF during heating operation, the fan
speed drops down to LL (breeze).
Specification outline
<COOL>
Ta ( °F)
Ta ( °C)
+5.4
+3.0
+4.5
+2.5
+3.6
+2.0
+2.7
+1.5
+1.8
+1.0
+0.9
+0.5
Tsc
Tsc
–0.9
–0.5
operation.
Speed modes shown in < > apply to cooling operation under AUTO air
conditioner operation mode.
each time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
temperature gradient) is chosen.
fan speed stays the same.
Ta (°F)
Ta (°C)
(–0.5) –1.0
(–0.9) –1.8
(0) Tsh
(0) Tsh
(+0.9) +1.8
(+0.5) +1.0
(+1.8) +3.6
(+1.0) +2.0
(+2.7) +5.4
(+1.5) +3.0
(+3.6) +7.2
(+2.0) +4.0
each time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
temperature gradient) is chosen.
fan speed stays the same.
A
HH
B
<HH>
C
H+ <HH>
D
H <HH>
L+ <H+>
E
L <H>
L <H>
F
L <L+>
G
L <L+>
L+ <H>
H <H+>
H+
<HH>
HH
<HH>
< > : Indicate automatic heating.
Body thermostat works.
Remote controller thermostat works.
- 23 -
Remarks
HH > H+ > H >
L+ > L > UL
or LL
DN code "32"
"0000": Body
thermo
"0001": Remote
controller thermo
E
D
C
B
A
TC2: Indoor heat
exchanger sensor
temperature
"HEATING
STANDBY
displayed
"