Environmental Considerations; Power Connections - weintek MT-6070iH3 Series Installation Instruction

Table of Contents

Advertisement

2.1.2 Making a NEMA-4 Mounting
Panel
The unit can be mounted into panels with a depth of 4"(105mm). It is recommended that
Details
the unit be mounted on the front panel of a steel enclosure, through an appropriate opening.
Allow a clearance of 1"(25mm) around the sides of the unit for mounting hardware. Allow
clearance for cable connections to the back of the unit. Unit depth may vary according to
cable type used. Typically, plan a depth to accommodate at least 4"(105mm) behind the
panel. This device should be mounted in the vertical position and for use on the flat surface
enclosure.
NEMA-4
Put the unit through the panel cut out. Slide the clamps (packed with product) into every
Mounting
hole provided around the case. Tighten the clamping screws in an even pattern until the
unit is secured in the panel. Screw Torque: 2.6~3.5 lbf.in. (For reaching waterproof effect
and to prevent the panel from being deformed.)
VESA
There are 4 holes on back panel for locking VESA, The screw: M4 P0.7mm, length:
Mounting
shorter then 8.0mm, and screw torque: 2.6 lbf.in.
Caution!
Do not over tighten mounting clamps!
Note:
Specifications
Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and
panel cannot flex more than 0.010".

2.1.3 Environmental Considerations

The MT6070iH3 are to be used indoors as built in displays. Make sure that the displays
are installed correctly and that the operating limits are followed (See Specifications).
Do not operate the unit in areas subject to explosion hazards due to flammable gases,
vapors or dusts.
The unit should not be installed where fast temperature variations and/or high humidity
are present. This will cause condensation of water in the device.
Do not install these terminals in environments where have inflammable gases.

2.2 Power Connections

Make sure that all local and national electrical standards are met when installing the unit.
Contact your local authorities to determine which codes apply.
2.2.1 Power Requirements
Power
Fusing
Requirements
Caution
High Voltage
The MT6070iH3 can be powered by DC power only. The specified
voltage range is 24±20% Volts DC. This insures compatibility with most
controller DC systems.
The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as
700mA.
If the display does not come on within 5 seconds of power up, remove
power. An internal fuse will prevent damage if the polarity of the DC
power is incorrect. Check wiring to insure proper connections and try to
power up again.
An Internal fuse will prevent damage for over voltage condition however
it isn't guaranteed.
DC voltage sources should provide proper isolation from main AC power
and similar hazards.