Optional Parts; 11-1.Remote Controller - Mitsubishi Electric City Multi PWFY-P36NMU-E-BU Data Book

Air conditioning systems
Hide thumbs Also See for City Multi PWFY-P36NMU-E-BU:
Table of Contents

Advertisement

11. OPTIONAL PARTS

11-1. Remote controller
11. OPTIONAL PARTS
PAR-W21MAA specifications
Item
ON/OFF
Operation mode switching
Water temperature setting
Preset temperature range
Water temperature display
Permit/Prohibit
local operation
Weekly scheduler
Error
Self check (Error history)
Test run
Circulating water
replacement warning
LANGUAGE setting
Operation locking function
MEES20K028
ON and OFF the operation of a group of units
Switches between Hot Water/Heating/Heating ECO/Anti-freeze/Cooling
* Available operation modes vary depending on the unit to be connected.
* Switching limit setting can be made via a remote controller.
Temperature can be set within the ranges below. (in increments of 1°F or 1°C)
Hot Water
87°F (30°C) min. ~ 158°F (70°C) max.
Heating
87°F (30°C) min. ~ 122°F (50°C) max.
Anti-freeze
50°F (10°C) min. ~ 113°F (45°C) max.
Cooling
50°F (10°C) min. ~ 87°F (30°C) max.
* The settable range varies depending on the unit to be connected.
Preset temperature range setting can be limited via a remote controller.
50°F (10°C) min. ~ 194°F (90°C) max.
(in increments of 1°F or 1°C)
* The settable range varies depending on the unit to be connected.
Individually prohibits operations of each local remote control function :ON/OFF,
Operation modes,water temperature setting, Circulating water replacement
warning reset.
* Upper level controller may not be connected depending on the unit to be connected.
ON/OFF/Water temperature setting can be done up to 6 times one day in the week.
(in increments of a minute)
When an error is currently occurring on a unit, the afflicted unit and the error code
are displayed.
Searches the latest error history by pressing the CHECK button twice.
Enables the Test run mode by pressing the TEST button twice.
* Test run mode is not available depending on the unit to be connected.
Displays the circulating water replacement warning via the unit message.
Clears the display by pressing the CIR.WATER button twice.
* Circulating water replacement warning is not available depending on the unit to
be connected.
The language on the dot matrix LCD can be changed. (Seven languages)
English/German/Spanish/Russian/Italian/French/Swedish
Remote controller operation can be locked or unlocked.
·All-switch locking
·Locking except ON/OFF switch
Description
AIR TO WATER
: Each group
: Not available
Operations
Display
40

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents