61000-4-6
61000-4-8
61000-4-29
61000-4-11
61000-4-12
61000-4-16
61000-4-17
IEC 60255-5
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS940G meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
RUGGEDCOM RS940G
Installation Manual, 01/2021, C79000-G8976-1036-07
Test
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
6.2 EMC and Environmental Type Tests
Description
Signal Ports
D.C Power
Ports
AC Power
Ports
Earth
ground Ports
Enclosure
Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
DC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Test Levels
10 V
10 V
10 V
10 V
40 A/m continuous,
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
10%
2 kVAC (Fail-
Safe Relay output)
2 kV
2 kV
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV
Certification
Severity
Levels
3
3
3
3
3
3
3
4
4
3
35