Dip Switches - HID Mercury LP1501 Installations And Specifications

Table of Contents

Advertisement

Powering
Trusted Identities
2.2 Jumpers
Jumpers
Set at
Description
J1
N/A
Factory use only
J3
PoE
LP1501 powered from the Ethernet connection
12V
LP1501 powered from a local 12 V DC power source connected to TB4-3 (VIN), TB4-4 (GND)
J4
N/A
Factory use only
J5
N/A
Micro USB port (2.0)
J6
N/A
10-Base-T/100Base-TX Ethernet connection
J7
 
Cabinet tamper switch input: short = tamper secure
J8
N/A
microSD card

2.3 DIP switches

The four switches on the S1 DIP switch configure the operating mode of the LP1501 processor. DIP switches
are read on power-up except where noted.
1
2
3
OFF
OFF
OFF
OFF
ON
X
X
OFF
ON
X
OFF
ON
ON
X
OFF
ON
ON
OFF
OFF
X
X
X
Note:  All other switch settings are unassigned and reserved for future use. X = don't care.
2.4 Factory default communication parameters
Interface 1 (NIC1)
Network: static IP address
Subnet mask
Default gateway
DNS server
Primary host port
Alternate host port
PLT-05243, A.1
4
Definitions
Normal operating mode.
X
After initialization, enable default User Name (admin) and Password (password). The
switch is read on the fly, a re-boot is not required. See
information.
Use factory default communication parameters.
Use OEM default communication parameters. Contact system manufacture for details.
See
2.5 Bulk erase configuration
Bulk erase prompt mode at power up. See
ON
Makes the LP1501 report and function like an EP1501. To be used in situations where the
host software has not been updated to support the LP series product line.
192.168.0.251
255.255.0.0
192.168.0.1
192.168.0.1
IP server, Data security: TLS if Available, port 3001, communication address: 0
Disabled
memory.
2.5 Bulk erase configuration
7
HID Mercury™ LP1501 Controller
Installation and Specifications
2.13 IT security
for additional
memory.
June 2021

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents