RMG GSM1SPAT Installation Manual page 4

Single/three phase wireless mobile water level controller

Advertisement

Trouble shooting:
Power Fail:
 Check whether input supply is correctly given.
 Check whether the GSM power switch position is "ON".
 Check fuse is in good condition. If fuse is failed or burnt replace it with 300 Milliamps.
Don't use more than that.
Motor not switching ON:
 Start Relay:
Check whether connection of start relay (Blue pair wire) is properly given.
Check start relay - It must be Normally Open. Start relay will become closed for 1-3
seconds while motor ON. Verify it using continuity tester or Multi-meter.
Motor not switching OFF:
 Stop Relay:
Check whether connection of stop relay (Black pair wire) is properly given.
Check stop relay - It must be Normally Closed. Stop relay will become open for 3
seconds while motor OFF. Verify it using continuity tester or Multi-meter.
SMS/CALL not working:
 SIM card:
Check if SIM card is properly inserted as per the image shown in the GSM unit.
Make sure that SIM Card has 2G support. Don't use SIM Cards that support 4G alone
like JIO SIM.
 GSM antenna location:
Keep it outside and don't enclose it.
 Antenna wire laying:
Make sure that GSM antenna wire is laid separately. Don't take it along with power
wires.
 GSM signal LED:
Check if it is blinking for every 3 seconds – Network connected.
If blinking every 1 second – Network Issue – Change another good network SIM card.
NOTE: For further assistance please do contact us on what's app 9940594413.
Web: www.rmgautomation.com
eMail: rmgworld@hotmail.com
GSM1SPAT - Installation Manual
Mobile: +91 99405 94413
4