For the 4x configurable inputs (which will be set to be digital inputs)
Input
Label
IN01
IN02
Temp Alarm
IN03
IN04
E.R.
0 = No wire link applied to the input,
1 = Link applied to the input.

5.5. Initial Power ON

When the wiring and configuration is complete power can be applied to the unit. The power indicator on the front panel
will light up to indicate the unit is powered.

5.6. Status Indicators

5.6.1. Fault LED

On the front panel below the power LED there is a Fault LED which will illuminate whilst a fault is present. The
conditions which cause the unit to go into fault are:
-
A communication fault between MelCOMMS MINI and one or more MelcoBEMS MINI (A1M) units.
-
A fault code read from any MelcoBEMS MINI (A1M) unit which is not 8000 (8000 = OK).

5.6.2. Buzzer

The buzzer will activate at the same time as the Fault LED. However, the buzzer can be muted by pressing the 'Mute'
pushbutton. The buzzer will stay muted until a new fault is present after all faults have been cleared.

5.6.3. Relay Status LEDs

Inside the enclosure on the PCB there are four LEDs which provide the status of each of the four relays. When the LED
is OFF the relay is de-energised, when the LED is ON the relay is energised.
The LED labelled 'Relay 3' is for the Fault Relay and the LED labelled 'Relay 4' is for the High Temp Relay.
Usage
High temperature alarm (ºC)
[IN01 | IN02 | IN03]
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
Error response
0 = Bring next unit ON
1 = Bring all units ON
0
= No high temp alarm
1
= 23
0
= 24
1
= 25
0
= 26
1
= 27
0
= 28
1
= Rotation test mode (1 min rotation)