Configuration - Procon MelCOMMS MINI Installation Manual

Table of Contents

Advertisement

5.4. Configuration

Note:
The MelCOMMS MINI unit must be restarted if any changes are made to the following configuration settings.
The configuration is done using the 12x DIP switches, 4x digital inputs and 4x configurable inputs (which are fixed as
digital inputs).
To help installers who are already familiar with the PANEL_RS product the 4x digital inputs on the MelCOMMS MINI
will be used as follows:
Digital
Digital
Input 03
Input 04
No link
No link
Link
No link
No link
Link
Link
Link
If links are fitted to both digital input IN03 and IN04 then custom settings will be applied. These custom settings are
determined by the 12x DIP switches and 4x configurable inputs.
The following shows the custom configuration options (Note: Value 0 = DIP switch OFF, Value 1 = DIP switch ON):
Settings
Units
name
connected
RS1
2
RS2
3
RS3
4
Custom
-
Units
Days
running
between
rotation
1
7
2
7
3
7
-
-
High
Setpoint
temperature
(ºC) /
alarm (ºC)
Mode
26
20 COOL
26
20 COOL
26
20 COOL
-
-