Page 4
Table of Contents Chapter 8 – Maintenance _____________________________________________________ 8-1 Preventive Maintenance Intervals __________________________________________________ 8-1 Maintenance Procedures __________________________________________________________ 8-2 How to clean the chamber interior and exterior. _______________________________________________ 8-2 How to listen for abnormal noise or vibration. ________________________________________________ 8-2 How to inspect the door seal. _____________________________________________________________ 8-2 How to inspect the refrigeration machinery compartment.
If the input voltage configuration is changed, this label must be replaced to reflect the new configuration. Replacement labels are available from TestEquity at no charge. ! CAUTION: This chamber must be properly configured for either 208 V or 230 V nominal input.
The independent EZ-Zone Limit Controller functions as the main protection device. ! CAUTION: The EZ-Zone Limit Controller has been properly configured by TestEquity to match the chamber’s system requirements. Improper modifications to these setup values can result in unreliable and unsafe operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing.
Page 7
! WARNING: This chamber operates at extreme temperatures. Avoid contact with air, objects, and surfaces that are hot or cold to prevent severe burns or frostbite. Protective gloves are recommended. TestEquity 1016C-1027C Temperature Chamber Page 1-3...
Chapter 2 – Installation Uncrating Inspect the shipping container for any signs of visible damage. Notify the carrier and TestEquity immediately if there are signs of shipping damage. The pallet is designed with ramps so the chamber can be rolled off without the need for a forklift or pallet jack.
230 V ±10% is present. 208 V - Wire T1 to 3 230 V - Wire T1 to 4 1 2 3 4 Control Transformer Figure 2-1 – Location of Input Configuration Terminals on the Electrical Sub Panel Page 2-2 TestEquity 1016C-1027C Temperature Chamber...
Phase Sequence This chamber has a protective circuit to ensure the proper input power phase sequence. If the chamber does not function with the initial wiring hookup, then reverse two of the input lines. TestEquity 1016C-1027C Temperature Chamber Page 2-3...
5. Turn the CONDITIONING Switch ON. Alternatively, turn the CONDITIONING Switch to the EVENT 1 position and turn the Power button on the F4T controller ON or EVENT 1 on the F4 controller ON. TestEquity 1016C-1027C Temperature Chamber Page 3-1...
The COOL Light will illuminate when the Temperature Controller turns on the cooling valve to maintain the workspace temperature. The COOL Light will cycle on/off as the workspace temperature approaches and reaches the temperature set point. Page 3-2 TestEquity 1016C-1027C Temperature Chamber...
Limit Controller’s temperature limits are exceeded. ! CAUTION: To prevent damage to your test sample and the chamber’s compressors, do not exceed the live load rating of the chamber. Live Load Capacity for Model 1016C and 1027C Temp +23°C 0°C –40°C...
Make sure that all connectors, wiring, pc boards, and auxiliary components can withstand the temperature extremes that they will be subjected to. In some cases, these components may not be able to last after repeated tests and should be considered expendable. Page 3-4 TestEquity 1016C-1027C Temperature Chamber...
Not all features or functions are applicable. Only the capabilities of a model PM6L1AJ-AAAABAA are applicable. ! CAUTION: The EZ-Zone Limit Controller has been properly configured by TestEquity to match the chamber’s system requirements. Improper modifications to these setup values can result in unreliable and unsafe operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing.
Then, you must press the RESET or EZ Key to resume normal operation. Silencing the Audible Alarm Turning off the CONDITIONING switch on the chamber front panel lets you temporarily turn off the Audible Alarm, even though the High or Low Limit condition may still exist. Page 4-2 TestEquity 1016C-1027C Temperature Chamber...
3. Locate the Terminal Strip on the electrical sub panel. Connections to the safety contacts are at terminals A1 and A2. Terminal Strip A1 A2 Figure 4-2 – Location of Safety Contact Connections on the Electrical Sub Panel TestEquity 1016C-1027C Temperature Chamber Page 4-3...
A suggested starting setting is 4 SCFM. Relief Vent Excess pressure in the chamber workspace is vented through a pressure-relief check-valve, which is located on the top of the chamber. There is no need to vent this externally. TestEquity 1016C-1027C Temperature Chamber Page 5-1...
Outside North America, most countries have 50 Hz. Standard three phase voltage systems in most 50 Hz countries are typically 380 V or 400 V. Please call TestEquity for details on voltage reducing transformers for 50 Hz operation. Note that the cooling performance will be reduced by 17% at 50 Hz.
Page 24
“How to inspect the refrigeration machinery compartment” and “How to check the refrigerant charge” before placing the chamber back into service to make sure that no damage has occurred. Page 6-2 TestEquity 1016C-1027C Temperature Chamber...
Page 25
Can/Should I put a filter in front of the condenser air inlet? No, TestEquity does not recommend this. Just follow the maintenance procedures and clean the condenser fins periodically.
Chapter 7 – Specifications Chapter 7 – Specifications Model 1016C Chamber Specifications Temperature Range –73°C to +175°C Control Tolerance ±0.5°C (±0.2°C Typical) (Measured at the control sensor after stabilization) Uniformity ±1.0°C (Variations throughout the chamber after stabilization) Live Load Capacity @ +23°C...
Operation at higher ambient temperatures may result in decreased cooling performance. Additional ports and shelves will also affect performance. Operation above 30°C (85°F) or below 16°C (60°F) ambient is not recommended. Page 7-2 TestEquity 1016C-1027C Temperature Chamber...
• Inspect the refrigeration machinery compartment. • Check the low-stage refrigeration charge. • Verify the chamber performance. Every 6 Months • Inspect the electrical compartment. • Clean the condenser. Every 12 Months • Verify the calibration. TestEquity 1016C-1027C Temperature Chamber Page 8-1...
• If the seal is still loose on the hinge side, adjust the door hinge. The hinges have slotted holes (on the door side) to permit adjustment. Page 8-2 TestEquity 1016C-1027C Temperature Chamber...
After verifying that there is no leak, you may need to top-off the charge if the pressure is too low. This note only applies to systems that have been evacuated and recharged. TestEquity 1016C-1027C Temperature Chamber Page 8-3...
These tests assume that the Temperature Controller’s setup and tuning values have not been changed from the values as shipped from TestEquity. Also, the Limit Controller high limit must be set to over +85°C (+88°C would be fine), and the low limit set to –75°C.
TestEquity recommends verifying the calibration before attempting to actually perform a calibration. The state-of-the-art instrumentation used in TestEquity chambers is of the highest quality and seldom goes out of calibration. If you try to calibrate the instrumentation before determining that calibration is necessary, you may make it worse if done incorrectly.
Page 34
For the F4T Controller: If calibration of the temperature controller is necessary, refer to the “F4T Touch Screen Controller User’s Guide”. For the F4 Controller: If calibration of the temperature controller is necessary, refer to the “F4 Temperature Controller User’s Manual”. Page 8-6 TestEquity 1016C-1027C Temperature Chamber...
As the high pressure vapor passes through the condenser, it is cooled by a fan, which blows ambient air across the finned condenser surface. The vapor condenses into a liquid and the cycle is repeated. TestEquity 1016C-1027C Temperature Chamber Page 8-7...
Page 36
The low-stage compressor turns on 30 seconds after the high-stage turns on through Timing Module TM1. This reduces the system’s starting current, while allowing the cascade condenser to get cool before the low-stage turns on. Page 8-8 TestEquity 1016C-1027C Temperature Chamber...
Solenoid Valve SV1 may be all the time. defective. DPS2 trips. Trips when the cool light cycles Solenoid valve SV2 may be from ON to OFF. defective. Hot gas bypass regulator may be defective or set too low. TestEquity 1016C-1027C Temperature Chamber Page 8-9...
Page 38
Chamber has been off for Crankcase heater defective several hours or more, and is (open). connected to source of power and main disconnect switch is on during that time. Page 8-10 TestEquity 1016C-1027C Temperature Chamber...
These are NOT do-it-yourself instructions! R-404A High-Stage Charge TestEquity does NOT recommend charging the system by relying on a clear sight glass only. Although a clear sight glass generally means the system is fully charged, it can be misleading.
Chapter 8 – Maintenance Recommended Spare Parts Replacement parts are available from TestEquity. Parts are generally in-stock and ready for immediate shipment. Next-day delivery is always available. If you cannot risk being out of service for even one day, then you should purchase critical spare parts in advance. Although most parts are standard and available from a variety of local distributors, some parts are either harder to find or custom.
Improper modifications to these setup values can result in erratic performance and unreliable operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing. If there is any doubt, please call TestEquity before proceeding. Setup Menu Prompt...
If the repair or replacement is performed in the FIRST YEAR from the date of invoice, TestEquity will also pay for the labor associated with the repair at the Purchaser's site, subject to TestEquity’s prior approval. During the SECOND and THIRD YEAR of the warranty period, Purchaser will be responsible for the installation and cost of installation of replacement or repaired parts.
Need help?
Do you have a question about the 1016C and is the answer not in the manual?
Questions and answers