Page 4
Table of Contents Chapter 7 – Maintenance _____________________________________________________ 7-1 Preventive Maintenance Intervals __________________________________________________ 7-1 Maintenance Procedures __________________________________________________________ 7-2 How to clean the chamber interior and exterior _______________________________________________ 7-2 How to listen for abnormal noise or vibration ________________________________________________ 7-2 How to inspect the door seal ______________________________________________________________ 7-2 How to inspect the refrigeration machinery compartment _______________________________________ 7-3 How to check the low-stage refrigerant charge ________________________________________________ 7-3 How to check the high-stage refrigerant charge _______________________________________________ 7-3...
If the input voltage configuration is changed, this label must be replaced to reflect the new configuration. Replacement labels are available from TestEquity at no charge. ! CAUTION: This chamber must be properly configured for either 208 V or 230 V (240 V) nominal input.
Page 6
! WARNING: Nitrogen gas is heavier than air. It makes up about 78% of the Earth’s standard atmosphere, is non-toxic, colorless, odorless, and tasteless. Pure nitrogen gas in a closed area can present an asphyxiation hazard (suffocation) without warning. Page 1-2 TestEquity 3007C Temperature Chamber...
The independent EZ-Zone Limit Controller functions as the main protection device. ! CAUTION: The EZ-Zone Limit Controller has been properly configured by TestEquity to match the chamber’s system requirements. Improper modifications to these setup values can result in unreliable and unsafe operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing.
Page 8
! WARNING: Nitrogen gas is heavier than air. It makes up about 78% of the Earth’s standard atmosphere, is non-toxic, colorless, odorless, and tasteless. Pure nitrogen gas in a closed area can present an asphyxiation hazard (suffocation) without warning. Page 1-4 TestEquity 3007C Temperature Chamber...
Chapter 2 – Installation Uncrating Inspect the shipping container for any signs of visible damage. Notify the carrier and TestEquity immediately if there are signs of shipping damage. The pallet is designed with ramps so the chamber can be rolled off without the need for a forklift or pallet jack.
208 V –5/+10% or 230 V ±10% is present. 208 V - Wire TA to 3 230 V - Wire TA to 4 1 2 3 4 Control Transformer Figure 2-1 – Location of Input Configuration Terminals on the Electrical Sub Panel Page 2-2 TestEquity 3007C Temperature Chamber...
Phase Sequence This chamber has a protective circuit to ensure the proper input power phase sequence. If the chamber does not function with the initial wiring hookup, then reverse two of the input lines. TestEquity 3007C Temperature Chamber Page 2-3...
This connection is a 3/8-inch JIC (Joint Industrial Council) stainless steel 37-degree flare fitting rated for very low temperature operation. The fitting is mounted on a non-metallic thermal breaker to help limit frost formation and condensation. Page 2-4 TestEquity 3007C Temperature Chamber...
Page 13
• The vent at the top of the chamber can discharge directly into the factory. If desired, the vent can be extended upward approximately two feet with a length of insulated tubing to prevent frost buildup on the top of the chamber. TestEquity 3007C Temperature Chamber Page 2-5...
4. Load your test sample in the chamber. 5. Turn the CONDITIONING Switch ON. Alternatively, turn the CONDITIONING Switch to the EVENT 1 position and turn the Power button on the F4T controller or EVENT 1 on the F4 controller ON. TestEquity 3007C Temperature Chamber Page 3-1...
The COOL Light will illuminate when the Temperature Controller turns on the cooling valve to maintain the workspace temperature. The COOL Light will cycle on/off as the workspace temperature approaches and reaches the temperature set point. Page 3-2 TestEquity 3007C Temperature Chamber...
Foam port plugs are provided with a gray silicone surface on one side. The port plug must be inserted with the gray silicone surface facing the inside of the chamber. Port plugs should be considered expendable and be replaced when they no longer provide a good seal. TestEquity 3007C Temperature Chamber Page 3-3...
Make sure that all connectors, wiring, pc boards, and auxiliary components can withstand the temperature extremes that they will be subjected to. In some cases, these components may not be able to last after repeated tests and should be considered expendable. Page 3-4 TestEquity 3007C Temperature Chamber...
SCFM. The flow of purge gas should be adjusted to the minimum amount required to obtain the desired drying in the chamber for your particular conditions. A suggested starting setting is 4 SCFM. TestEquity 3007C Temperature Chamber Page 3-1...
4. The event outputs are just switches. You must provide power from an external source. 5. A 1/2-inch conduit hole is provided on the left side of the lower door to route your wires through. Use the appropriate wire/cable management fittings. Page 3-2 TestEquity 3007C Temperature Chamber...
Not all features or functions are applicable. Only the capabilities of a model PM6L1AJ-AAAABAA are applicable. ! CAUTION: The EZ-Zone Limit Controller has been properly configured by TestEquity to match the chamber’s system requirements. Improper modifications to these setup values can result in unreliable and unsafe operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing.
Then, you must press the RESET or EZ Key to resume normal operation. Silencing the Audible Alarm Turning off the CONDITIONING switch on the chamber front panel lets you temporarily turn off the Audible Alarm, even though the High or Low Limit condition may still exist. Page 4-2 TestEquity 3007C Temperature Chamber...
3. Locate the Terminal Strip on the electrical sub panel. Connections to the safety contacts are at terminals A1 and A2. A1 A2 Figure 4-2 – Location of Safety Contact Connections on the Electrical Sub Panel TestEquity 3007C Temperature Chamber Page 4-3...
Outside North America, most countries have 50 Hz. Standard three phase voltage systems in most 50 Hz countries are typically 380 V or 400 V. Please call TestEquity for details on voltage reducing transformers for 50 Hz operation. Note that the cooling performance will be reduced by 17% at 50 Hz.
Page 26
“How to inspect the refrigeration machinery compartment” and “How to check the refrigerant charge” before placing the chamber back into service to make sure that no damage has occurred. Page 5-2 TestEquity 3007C Temperature Chamber...
Page 27
Can/Should I put a filter in front of the condenser air inlet? No, TestEquity does not recommend this. Just follow the maintenance procedures and clean the condenser fins periodically.
Operation at higher ambient temperatures may result in decreased cooling performance. Additional ports and shelves will also affect performance. Operation above 30°C (85°F) or below 16°C (60°F) ambient is not recommended. TestEquity 3007C Temperature Chamber Page 6-1...
• Check the low-stage refrigeration charge. • Check the high-stage refrigeration charge. • Verify the chamber performance. Every 6 Months • Inspect the electrical compartment. • Clean the condenser. Every 12 Months • Verify the calibration. TestEquity 3007C Temperature Chamber Page 7-1...
• If the seal is still loose on the hinge side, adjust the door hinge. The hinges have slotted holes (on the door side) to permit adjustment. Page 7-2 TestEquity 3007C Temperature Chamber...
4. If you see bubbles or it appears partially full, then this indicates that there is probably a leak. 5. When the Temperature Controller is cycling (Cool Light cycles on/off), the sightglass may appear 1/2 to 2/3 full. This is normal. TestEquity 3007C Temperature Chamber Page 7-3...
These tests assume that the Temperature Controller’s setup and tuning values have not been changed from the values as shipped from TestEquity. Also, the Limit Controller high limit must be set to over +85°C (+88°C would be fine), and the low limit set to –75°C.
TestEquity recommends verifying the calibration before attempting to actually perform a calibration. The state-of-the-art instrumentation used in TestEquity chambers is of the highest quality and seldom goes out of calibration. If you try to calibrate the instrumentation before determining that calibration is necessary, you may make it worse if done incorrectly.
Page 36
For the F4T Controller: If calibration of the temperature controller is necessary, refer to the “F4T Touch Screen Controller User’s Guide”. For the F4 Controller: If calibration of the temperature controller is necessary, refer to the “F4 Temperature Controller User’s Manual”. Page 7-6 TestEquity 3007C Temperature Chamber...
The hot, high pressure vapor is forced out of the compressor discharge valve and into the condenser. As the high pressure vapor passes through the condenser, it is cooled by a fan, which blows ambient air TestEquity 3007C Temperature Chamber Page 7-7...
Page 38
The low-stage compressor turns on 30 seconds after the high-stage turns on through Timing Module TM1. This reduces the system’s starting current, while allowing the cascade condenser to get cool before the low-stage turns on. Page 7-8 TestEquity 3007C Temperature Chamber...
Low charge (leak). temp is reduced. DPS2 trips. Trips when the cool light cycles Solenoid valve SV2 may be from on to off. defective. Hot gas bypass regulator may be defective or set too low. TestEquity 3007C Temperature Chamber Page 7-9...
Page 40
If tuning PID control parameters Control parameters may need to in temperature controller are as be changed for your unique test shipped from TestEquity and conditions. R-508B hot gas only occurs in cool mode. bypass regulator may be defective or set too high.
These are NOT do-it-yourself instructions! R-404A High-Stage Charge TestEquity does NOT recommend charging the system by relying on a clear sight glass only. Although a clear sight glass generally means the system is fully charged, it can be misleading.
Chapter 7 – Maintenance Recommended Spare Parts Replacement parts are available from TestEquity. Parts are generally in-stock and ready for immediate shipment. Next-day delivery is always available. If you cannot risk being out of service for even one day, then you should purchase critical spare parts in advance. Although most parts are standard and available from a variety of local distributors, some parts are either harder to find or custom.
Style 66, #0066000008 300015 Blower Wheel, CW CUSTOM Required when replacing circulator motor 382498 Blower Wheel, CCW CUSTOM Required when replacing circulator motor 382499 Seal, Fan Motor Shaft CUSTOM Required when replacing circulator motor 300286 Page 7-14 TestEquity 3007C Temperature Chamber...
Improper modifications to these setup values can result in erratic performance and unreliable operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing. If there is any doubt, please call TestEquity before proceeding. Setup Menu Prompt...
If the repair or replacement is performed in the FIRST YEAR from the date of invoice, TestEquity will also pay for the labor associated with the repair at the Purchaser's site, subject to TestEquity’s prior approval. During the SECOND and THIRD YEAR of the warranty period, Purchaser will be responsible for the installation and cost of installation of replacement or repaired parts.
Need help?
Do you have a question about the FastRate 3007C and is the answer not in the manual?
Questions and answers