Power Module Check - Daikin FTK Series Service Manual

Inverter split wall mounted type
Table of Contents

Advertisement

DAMA-SM-21-001

5.11 Power Module Check

Check No.22
Check to make sure that the voltage between (+) and (–) of the power module is approximately
0 V before checking.
 Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
 Follow the procedure below to measure resistance between the (+) or (–) terminal of the
Positive terminal (+) of
digital multimeter
Negative terminal (–) of
digital multimeter
Resistance is OK.
Resistance is NG.
Service Diagnosis
connector, press the protrusion on the connector.
power module and the U, V, or W terminal of the compressor with a multimeter. Evaluate the
measurement results referring to the following table.
Power module
Diagram Power Module Check for FTK(X)09/12
Diagram Power Module Check for FTK(X)18/24
UVW
(+)
Power module
UVW
(+)
several kΩ ~ several MΩ
0 Ω or ∞
Actuator Check
Power module
UVW
(–)
Power module
UVW
(–)
94