Page 1
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K AL1301 IO-Link: 1.1.2 ifm firmware: 2.1.28 or higher LR DEVICE: 1.3.1.x or higher English...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Content Table of Contents Preliminary note Legal and copyright information ................... 5 Purpose of the document ..................... 5 Symbols and styles used .....................
Page 3
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Content Configuration LR DEVICE ........................22 8.1.1 Remarks ............................. 23 8.1.2 IoT: Configure access rights ....................... 24 8.1.3...
Page 4
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Content 13.1.5 Outputs ............................64 13.1.6 Interfaces ............................ 64 13.1.7 Operating conditions ........................65 13.1.8 Approvals / tests .........................
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Preliminary note Legal and copyright information Preliminary note Legal and copyright information ....................... 5 Purpose of the document ......................... 5 Symbols and styles used ..........................
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Preliminary note Symbols and styles used > Symbols and styles used 15989 WARNING Death or serious irreversible injuries may result.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Safety instructions General Safety instructions General ..............................7 Required background knowledge ......................7 Safety symbols on the device ........................7 Tampering with the unit ..........................
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Safety instructions Tampering with the unit > Tampering with the unit 11242 WARNING Tampering with the units can affect the safety of operators and machinery! Tampering with the units is not allowed.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Intended use Permitted use Intended use Permitted use ............................9 Prohibited use ............................9 18761 >...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Function Prohibited use Function Communication, parameter setting, evaluation ..................11 Digital inputs ............................12 IO-Link supply ............................12...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Function Digital inputs > 4.1.5 Visual indication 7772 The device has the following visual indicators: ...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Mounting Mount the device Mounting Mount the device ............................13 22016 > Mount the device 15540 ►...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Electrical connection PROFINET ports > PROFINET ports 17849 ► Connect the device via the M12 socket X21 and/or X22 to the PROFINET network (e.g.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Electrical connection IO-Link ports > IO-Link ports 8526 Ports X01...X04: For use as IO-Link port class A: ►...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Electrical connection Connect the device > Connect the device 17542 ► Disconnect power. ► Connect the device via M12 socket X31 to 24 V DC (20...28 V SELV/PELV;...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Operating and display elements Overview Operating and display elements Overview ..............................18 LED indicators ............................19 5440 >...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Operating and display elements LED indicators > LED indicators 22024 The device only has the following LED indicators: >...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Operating and display elements LED indicators > 7.2.3 IoT port 7722 The IoT port (X23) has the 3 LNK, ACT and IoT LEDs. The LEDs indicate the status of the Ethernet connection and the device identification.
Page 21
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LED indicators Configuration LR DEVICE .............................22 PROFINET..............................32 IoT Core ..............................42 22367...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > LR DEVICE Remarks ..............................23 IoT: Configure access rights ........................24 IoT: Configure IP settings ........................25 IoT: Configure the interface to the LR SMARTOBSERVER ..............26...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.2 IoT: Configure access rights 16555 The access rights define which instance may read and / or write the parameter data, process data and event/diagnostic messages.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.3 IoT: Configure IP settings 17713 For access to the IO-Link master via the IT infrastructure the user has to set the IP settings of the IoT port.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.4 IoT: Configure the interface to the LR SMARTOBSERVER 16552 To enable data transfer between the device and the LR SMARTOBSERVER monitoring software, the LR SMARTOBSERVER monitoring software interface has to be configured.
Page 27
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE The user can decide separately for each IO-Link port if the process data of the connected IO-Link devices should be transferred to the LR SMARTOBSERVER.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.7 IO-Link ports: Configure operating mode 17439 The IO-Link ports X01...X04 of the device support the following operating modes: ...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.8 IO-Link ports: Set the device validation and data storage 17945 In the operating mode "IO-Link"...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE 8.1.9 Firmware: Reset device to factory settings 7209 When the IO-Link master is reset, all parameters are set to the factory settings: To reset the device to factory settings: ►...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration LR DEVICE > 8.1.11 Configure IO-Link devices 11033 To configure the IO-Link devices connected to the device with the LR DEVICE parameter setting...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.1 Install GSD file 22410 To represent the AL1301 in a field bus projection software (e.g. STEP 7), ifm provides a GSD file. The user can download the GSD file from the ifm website (→...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.2 Add the IO-Link master to the PROFINET network 22406 The configuration of the PROFINET parameters is done via the PROFINET projection software.
Page 35
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET Add IO-Link ports ► Move the [4 Ports] node via drag&drop from the hardware catalogue to slot 1 of the AL1301.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.3 Configure access rights 22760 In order to configure the access rights to the device: Open device editor ►...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.4 Configure IO-Link ports 17306 In STEP 7, the following assignment of the PROFINET slots to the IO-Link ports of the device applies:...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET 8.2.5 Configure the PROFINET port 22761 In order to configure the Ethernet interface of the AL1301: Prerequisites >...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.7 Read and write data cyclically 17372 Mapping: IO-Link ► To check the validity of the cyclic process data, evaluate the PQI byte (→...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET > 8.2.9 PROFINET: Programmers' notes 12761 The programmer can access on the following data from the PLC application: ...
Page 41
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration PROFINET Configure IO-Link devices 1860 Symbol / function Description Remarks block IO_LINK_DEVICE / Acyclic access to the parameters of an IO-Link...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core 8.3.1 Configure IoT interface 16540 The parameters of the IoT port X23 are saved in the iotsetup substructure. The user can access the...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core 8.3.3 Configure IO-Link ports 16454 Parameters of the IO-Link ports of the IO-Link master are saved in the iolinkmaster/port[n] substructure.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > 8.3.5 Set application identification 16580 The application name of the IO-Link master is saved in the devicetag substructure. The user can...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > 8.3.8 Control IO-Link master 17963 The device can be controlled via the following services:...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > 8.3.10 Read information about IO-Link devices 16553 Information about an IO-Link device connected via an IO-Link port is saved in the iolinkmaster/port[n]/iolinkdevice/ substructure.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > 8.3.11 Examples Example: Read process data of an IO-Link device ................48 Example: Read several parameter values of the IO-Link master simultaneously ........49...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > Example: Read several parameter values of the IO-Link master simultaneously 17310 Task: The following current values are to be read by the IO-Link master.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > Example: Read the parameter value of an IO-Link device 16546 Task: Read the serial number of the ifm temperature sensor TN2531 at IO-Link port X02...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > Example: Subscribe to event 17946 Task: The current values of the following parameters should be sent regularly to a network server with IP address 192.168.0.4: product name of the IO-Link device at IO-Link port X02, cyclic input data of...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > 8.3.12 Programmers' notes ifm IoT Core: General information ......................52 Device description ..........................52 Access ifm-IoT Core ..........................53...
Page 53
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > Access ifm-IoT Core 17561 To activate the changes of the parameter values the IoT Core must have the respective write access rights to the IO-Link master (→...
Page 54
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > POST method 16548 Using the POST method the user has read and write access to a data point. A form with the required information is transferred to the IP address of the IO-Link master (IoT port X23).
Page 55
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Configuration IoT Core > IoT Core: Diagnostic codes 17437 The ifm IoT Core uses the following diagnostic codes:...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Operation Web interface: Read device and diagnostic information > Web interface: Read device and diagnostic information...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Maintenance Replace IO-Link device Maintenance 21577 The operation of the unit is maintenance-free. ► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this! ►...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Factory settings Replace IO-Link device Factory settings 16542 In the factory settings, the device has the following parameter settings:...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix Technical data > 13.1.4 Inputs 22820 Inputs Number of digital inputs 8; (IO-Link Port Class A: 4 x 2) Switching level high [V] 11...28 DC...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix Technical data > 13.1.10 Electrical connection 17850 Voltage supply IN X31 Plug and socket connection...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > 13.2 PROFINET Parameter data ............................67 Cyclic data ..............................70 Acyclic data ............................72 22433 >...
Page 68
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > Parameters of the IO-Link ports 22787 Parameter Description Possible values [Fail-safe mode]...
Page 69
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET Parameter Description Possible values Type compatible V1.1 IO-Link device is compatible with device with Restore the V1.1 IO-Link standard...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > 13.2.2 Cyclic data PROFINET modules ..........................70 PQI (Port Qualifier Information) ......................71 22429 >...
Page 71
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > PQI (Port Qualifier Information) 22686 Port Qualifier Information (PQI) contains diagnostic information about the IO-Link port. In addition to the process data, the IO-Link master sends the PQI to the PROFINET controller.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > 13.2.3 Acyclic data I&M datasets ............................72 Diagnostic and alarms ..........................74 22427 >...
Page 73
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET I&M3 (Slot 0) 22781 Variable Description Access* Size Descriptor Description of the device (ASCII, padded with spaces) * ...
Page 74
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix PROFINET > Diagnostic and alarms 22784 Name Description Type code 0x02 EVNT_CODE_M_PDU_CHECK Receive frame with CRC error...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > 13.3.1 Overview: IoT profile Profile: deviceinfo ...........................76 Profile: devicetag ............................77 Profile: iolinkmaster ..........................77...
Page 77
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core Profile: devicetag 17438 Element (identifier) Properties mandatory Comments devicetag type = structure ...
Page 78
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Profile: parameter 16545 The profile is used to mark the elements of type data as parameters (acyclic data). The profile defines no substructure.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > 13.3.2 Overview: IoT types 16547 The ifm IoT Core uses the following element types:...
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > 13.3.3 Overview: IoT services Service: factoryreset ..........................80 Service: gettree ............................80 Service: getdata ............................81...
Page 81
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: getdata 12223 Name: getdata Description: Service reads the value of a data point and provides it.
Page 82
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: getidentity 17134 Name: getidentity Description: The service reads the complete device description of the AL1301 and provides it as JSON object.
Page 83
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: iolreadacyclic 12222 Name: iolreadacyclic Description: The service acyclically reads the parameter value of an IO-Link device. It is accessed via IO-Link index and subindex.
Page 84
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: setblock 12224 Name: setblock Description: The service simultaneously sets the values of several data points of a structure.
Page 85
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: setelementinfo 7159 Name: setelementinfo Description: The service sets the uid of an element.
Page 86
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Appendix ifm IoT Core > Service: subscribe 10920 Name: subscribe Description: The service subscribes to the values of data points. The data points to be subscribed are transferred as a list.
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Index Index I&M datasets ..................72 I&M0 (Slot 0) ..................72 I&M0 (Slot 1) ..................73 Access ifm-IoT Core ................
Page 88
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1301) 05 / 2018 Index Parameters of the IO-Link ports ............68 Permitted use ................... 9 PI controller ....................5 Visual indication ..................