Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content Content Preliminary note Legal and copyright information ................... 6 Purpose of the document ..................... 6 Symbols and styles used ..................... 6 Modification history ......................7 Safety instructions General ..........................
Page 3
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content Configuration Remarks ..........................27 8.1.1 Supported configuration options ....................28 8.1.2 Connection possibilities ......................28 8.1.3 Offline parameter setting ......................31 8.1.4 VPN connection .......................... 31 LR DEVICE: Configure the device ..................32...
Page 4
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content 12.1.10 Electrical connection ........................65 12.2 Profinet ..........................66 12.2.1 Parameter data ........................... 67 12.2.2 Cyclic data ..........................70 12.2.3 Acyclic data ..........................73 Index ifm weltweit •...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Preliminary note Preliminary note Legal and copyright information ....................... 6 Purpose of the document ......................... 6 Symbols and styles used .......................... 6 Modification history ........................... 7...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Preliminary note > Modification history 13903 Version Topic Date New creation of document 2016-11-21 Update to LR DEVICE V1.1.0.87 2017-04-21...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions Safety instructions General ..............................9 Required background knowledge ......................9 Warnings used ............................9 Safety symbols on the device .........................10 Tampering with the unit ..........................10...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions > General 22068 The plant manufacturer is responsible for the safety of the plant in which the device is installed. If the device is used in a way that is not intended by the manufacturer, the protection supported by the device may be impaired.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions > Safety symbols on the device 15021 General warning When this symbol is shown, consult the corresponding section in the operating instructions.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Functions and features Functions and features Permitted use ............................11 Prohibited use ............................11 18761 > Permitted use 22052 The device has been designed for use without a control cabinet in plant construction.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Function > Digital inputs 7584 The device has 4 additional digital inputs (type 2 according to EN 61131-2). The digital inputs are on pin 2 of the IO-Link ports X01 ... X04.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Mounting Mounting Mount the device ............................15 22016 > Mount the device 15540 ► Disconnect the system from power before installation. ► For installation choose a flat mounting surface.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection Electrical connection Ethernet ports ............................17 IO-Link ports ............................18 Connect the device ..........................20 22017 A qualified electrician must connect the unit. ► Observe the national and international regulations for the installation of electrical equipment.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > Ethernet ports 22683 Connection possibilities Notes on connection possibilities: → (→ p. 28) ► Connect the unit via the M12 socket X21 and/or X22 with the Profinet network (e.g.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > IO-Link ports 22684 Ports X01...X04: For use as IO-Link port class A: ► Connect the connector of the IO-Link devices with the M12 sockets X01 ...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > 6.2.2 IO-Link circuits 11616 The IO-Link interfaces of the device meet the requirements of the IO-Link specification 1.0 to 1.1.2.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > Connect the device 2580 ► Disconnect power. ► Connect the device via M12 socket X31 to 24 V DC (20...30 V SELV/PELV; for cULus max. 24 V DC; according to EN61010-1, secondary circuit with maximum 30 V DC derived from applied voltage up to 300 V of overvoltage category II).
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements Operating and display elements Overview ..............................22 LED indicators ............................23 5440...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > Overview 22025 Status LEDs RDY, BF und SF Status LEDs → (→ p. 23) Status LEDs LNK and ACT of the...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > LED indicators 22024 The device only has the following LED indicators: > 7.2.1 Status LEDs 22034 The RDY LED shows the status of the gateway.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > 7.2.3 Voltage supply 22026 The interface for voltage supply (X31) has the LED that is marked as US. The LED indicates the status of the voltage supply.
Page 25
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements >...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.1.1 Supported configuration options 22408 The AL1100 can be configured using the following options: Parameter setting software LR DEVICE (version 1.0.x or higher) (art. no.: QA0011/QA0012) ...
Page 29
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Operation with Profinet connection (without LR DEVICE) 7396 Operation of the IO master as Profinet IO device. As an option, several IO-Link masters can be coupled via the Ethernet interfaces X21 and X22.
Page 30
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Operation with Profinet connection and LR DEVICE/LR SmartObserver 7398 The AL1100 can be connected via the two Ethernet interfaces X21 and X22 simultaneously with the Profinet control level (PLC) and the IT infrastructure level (monitoring/parameter setting).
22762 An active VPN connection blocks the access of the parameter setting software LR DEVICE to the Profinet interface of the AL1100. ► Deactivate the VPN connection in order to be able to access the AL1100 with the LR DEVICE.
Reset IO-Link master to factory settings ....................40 22402 The IO-Link master and the IO-Link devices connected to the AL1100 can be configured with the ifm software LR DEVICE. Further information about operation and functions of the LR DEVICE parameter setting software: ►...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.1 Set-up 12759 Factory settings On delivery, the AL1100 is configured with the → (→ p. 60) Before configuration with the LR DEVICE parameter setting software, the user must put the device into operation.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.2 Configure communication profile 22061 In order to copy the access rights to the device: ► Select the [LineRecorder] menu. >...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.3 Configure the Ethernet interface 22404 To set the parameters of the Profinet interface (X21/X22): ► Select the [Network] menu. >...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.4 Configure the interface to the SmartObserver 12743 In order to set the parameters of the interface to the SmartObserver: ► Select the [LineRecorder] menu.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.5 Set the operating mode of the IO-Link ports 8714 The IO-Link ports X01...X04 of the device support the following operating types: ...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.6 Set device validation and data storage 7165 In operating mode "IO-Link" the user can set the behaviour of the IO-Link ports regarding device validation and backup/restore of parameter data of the connected IO-Link devices.
Page 39
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Name Description Possible values Type compatible IO-Link device is compatible with V1.1 device with the V1.1 IO-Link standard Restore Verification whether it is an...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.7 Reset IO-Link master to factory settings 12740 Factory settings When resetting the AL1100, all parameters are reset to the →...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > LR DEVICE: Configure IO-Link devices 22403 In order to configure the IO-Link devices connected to the AL1100 using the parameter setting...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.3.1 Offline parameter setting: Add IO-Link devices manually 22817 The AL1100 supports the automatic recognition of IO-Link devices that are connected to the IO-Link interfaces.
Install GSD file 22410 To represent the AL1100 in a field bus projection software (e.g. STEP 7), ifm provides a GSD file. The user can download the GSD file from the ifm website (→ the GSD file, all parameters, process data, and their valid value ranges are defined.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.2 Add the device to the Profinet network 22406 The configuration of the Profinet parameters is done via the Profinet projection software.
Page 46
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Add IO-Link ports ► Move the [4 Ports] node via drag&drop from the hardware catalogue to slot 1 of the AL1100. > Step 7 shows available IO-Link interfaces. ► Save the project.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.3 Configure communication profile 22760 In order to configure the access rights to the device: Open device editor ► Open STEP-7 application "HW Konfig".
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.4 Configure IO-Link ports 22759 In STEP 7, the following assignment of the Profinet slots to the IO-Link ports of the device applies:...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.5 Configure the Profinet interface 22761 In order to configure the Ethernet interface of the AL1100: Prerequisites > AL1100 is correctly integrated in the Profinet project (→...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Profinet: Programmers' notes 12761 The programmer can access on the following data from the PLC application: Read device information of the AL1100 ...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Identify device 22816 In the online mode, the user can identify the device using the status LEDs RDY, BF und SF ►...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > 9.2.1 Web interface: Read device and diagnostic information 12744 In order to read the diagnostic information about the current device status via the web interface: ►...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > 9.2.2 LR DEVICE: Read device information 11614 To show information about the AL1100: ► Start LR DEVICE. ► Scan network for devices.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Reboot the device 12760 When restarting the device, all settings are kept. To restart the AL1100: ► Start LR DEVICE. ► Scan the network for devices.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Firmware update 22425 The new firmware is installed via the device's web interface. If the firmware update is not successful, deactivate all connections to the Profinet PLC, LR SmartObserver and LR DEVICE and repeat the process.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Exchange IO-Link device 7775 To exchange an IO-Link device: Requirement: > IO-Link device is with factory settings. > IO-Link device supports IO-Link standard 1.1 or higher.
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Maintenance Maintenance 21577 The operation of the unit is maintenance-free. ► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this! ►...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Factory settings Factory settings 22671 In the factory settings, the device has the following parameter settings: Parameters Factory setting [IP address] 0.0.0.0 [Subnet mask] 0.0.0.0...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.1.1 Application 23710 Application Application I/O modules for field applications Daisy-chain function Communication interface > 12.1.2 Electrical data 22819 Electrical data Operating voltage 20...30 DC;...
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.1.9 Mechanical data 22825 Mechanical data Weight [g] Materials Housing: PA; socket: brass nickel-plated > 12.1.10 Electrical connection 22826 Voltage supply IN X31...
Page 66
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2 Profinet Parameter data ............................67 Cyclic data ..............................70 Acyclic data ............................73 22433...
Page 67
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.1 Parameter data 22786 Slot Sub-slot Name Description Parameter of the IO-Link master Master Parameter data of the IO-Link master (→...
Page 68
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Parameters of the IO-Link ports 22787 Parameter Description Possible values [Fail-safe mode] Behaviour in case the Profinet No Fail Safe deactivated...
Page 69
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix Parameter Description Possible values Type compatible V1.1 IO-Link device is compatible with device with Restore the V1.1 IO-Link standard Verification whether it is an IO-Link...
Page 70
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.2 Cyclic data Profinet modules .............................71 PQI (Port Qualifier Information) ......................72 22429...
Page 71
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Profinet modules 22685 Module Description IO-Link 32 I/ 32 O + PQI 32 bytes input and output data and PQI IO-Link 16 I/ 16 O + PQI...
Page 72
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > PQI (Port Qualifier Information) 22686 Port Qualifier Information (PQI) contains diagnostic information about the IO-Link port. In addition to the process data, the IO-Link master sends the PQI to the Profinet controller.
Page 73
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.3 Acyclic data 22427 > I&M datasets 22778 The AL1100 supports the following I&M datasets (I&M = Identification & Maintenance): >...
Page 74
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > I&M3 (Slot 0) 22781 Variable Description Access* Size Descriptor Description of the device (ASCII, padded with spaces) * ... r/w = read and write >...
Page 75
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Diagnostic and alarms 22784 Name Description Type code 0x02 EVNT_CODE_M_PDU_CHECK Receive frame with CRC error Alarm 0x1B EVNT_CODE_S_RETRY Repetitions detected Alarm...
Page 76
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-04-21 Index Inputs / outputs ..................65 Index Install GSD file ..................45 Interfaces ....................66 IO-Link ....................14 IO-Link circuits ..................20 Acyclic data .................... 75 IO-Link ports ..................
Page 77
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-04-21 Index Required background knowledge ............9 Reset IO-Link master to factory settings ..........41 Safety instructions ................... 8 Safety symbols on the device ..............10 Set device validation and data storage ..........
Page 79