Operating Instructions
IO-Link Master with Profinet interface
StandardLine
4 Ports
IP 65 / IP 67
AL1100
ifm firmware: 1.1.22 or higher
LR DEVICE: 1.0.x or higher
IO-Link: 1.1.2
English

Advertisement

Table of Contents
loading

Summary of Contents for IFM AL1100

  • Page 1 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 AL1100 ifm firmware: 1.1.22 or higher LR DEVICE: 1.0.x or higher IO-Link: 1.1.2 English...
  • Page 2: Table Of Contents

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content Content Preliminary note Legal and copyright information ................... 6 Purpose of the document ..................... 6 Symbols and styles used ..................... 6 Modification history ......................7 Safety instructions General ..........................
  • Page 3 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content Configuration Remarks ..........................27 8.1.1 Supported configuration options ....................28 8.1.2 Connection possibilities ......................28 8.1.3 Offline parameter setting ......................31 8.1.4 VPN connection .......................... 31 LR DEVICE: Configure the device ..................32...
  • Page 4 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Content 12.1.10 Electrical connection ........................65 12.2 Profinet ..........................66 12.2.1 Parameter data ........................... 67 12.2.2 Cyclic data ..........................70 12.2.3 Acyclic data ..........................73 Index ifm weltweit •...
  • Page 5: Preliminary Note

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Preliminary note Preliminary note Legal and copyright information ....................... 6 Purpose of the document ......................... 6 Symbols and styles used .......................... 6 Modification history ........................... 7...
  • Page 6: Legal And Copyright Information

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Preliminary note > Legal and copyright information 1631 © All rights reserved by ifm electronic gmbh. No part of this manual may be reproduced and used...
  • Page 7: Modification History

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Preliminary note > Modification history 13903 Version Topic Date New creation of document 2016-11-21 Update to LR DEVICE V1.1.0.87 2017-04-21...
  • Page 8: Safety Instructions

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions Safety instructions General ..............................9 Required background knowledge ......................9 Warnings used ............................9 Safety symbols on the device .........................10 Tampering with the unit ..........................10...
  • Page 9: General

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions > General 22068 The plant manufacturer is responsible for the safety of the plant in which the device is installed. If the device is used in a way that is not intended by the manufacturer, the protection supported by the device may be impaired.
  • Page 10: Safety Symbols On The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Safety instructions > Safety symbols on the device 15021 General warning When this symbol is shown, consult the corresponding section in the operating instructions.
  • Page 11: Functions And Features

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Functions and features Functions and features Permitted use ............................11 Prohibited use ............................11 18761 > Permitted use 22052 The device has been designed for use without a control cabinet in plant construction.
  • Page 12: Function

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Function Function Communication, parameter setting, evaluation ..................13 Digital inputs ............................14 IO-Link supply ............................14 7482...
  • Page 13: Communication, Parameter Setting, Evaluation

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Function > Communication, parameter setting, evaluation IO-Link ..............................13 Profinet ..............................13 Parameter setting ...........................13 Visual indication ............................13 7485 > 4.1.1 IO-Link 7773 The device offers the following IO-Link functions: ...
  • Page 14: Digital Inputs

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Function > Digital inputs 7584 The device has 4 additional digital inputs (type 2 according to EN 61131-2). The digital inputs are on pin 2 of the IO-Link ports X01 ... X04.
  • Page 15: Mounting

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Mounting Mounting Mount the device ............................15 22016 > Mount the device 15540 ► Disconnect the system from power before installation. ► For installation choose a flat mounting surface.
  • Page 16: Electrical Connection

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection Electrical connection Ethernet ports ............................17 IO-Link ports ............................18 Connect the device ..........................20 22017 A qualified electrician must connect the unit. ► Observe the national and international regulations for the installation of electrical equipment.
  • Page 17: Ethernet Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > Ethernet ports 22683 Connection possibilities Notes on connection possibilities: → (→ p. 28) ► Connect the unit via the M12 socket X21 and/or X22 with the Profinet network (e.g.
  • Page 18: Io-Link Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > IO-Link ports 22684 Ports X01...X04: For use as IO-Link port class A: ► Connect the connector of the IO-Link devices with the M12 sockets X01 ...
  • Page 19: Io-Link Circuits

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > 6.2.2 IO-Link circuits 11616 The IO-Link interfaces of the device meet the requirements of the IO-Link specification 1.0 to 1.1.2.
  • Page 20: Connect The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Electrical connection > Connect the device 2580 ► Disconnect power. ► Connect the device via M12 socket X31 to 24 V DC (20...30 V SELV/PELV; for cULus max. 24 V DC; according to EN61010-1, secondary circuit with maximum 30 V DC derived from applied voltage up to 300 V of overvoltage category II).
  • Page 21: Operating And Display Elements

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements Operating and display elements Overview ..............................22 LED indicators ............................23 5440...
  • Page 22: Overview

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > Overview 22025 Status LEDs RDY, BF und SF Status LEDs → (→ p. 23) Status LEDs LNK and ACT of the...
  • Page 23: Led Indicators

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > LED indicators 22024 The device only has the following LED indicators: > 7.2.1 Status LEDs 22034 The RDY LED shows the status of the gateway.
  • Page 24: Voltage Supply

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements > 7.2.3 Voltage supply 22026 The interface for voltage supply (X31) has the LED that is marked as US. The LED indicates the status of the voltage supply.
  • Page 25 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operating and display elements >...
  • Page 26: Configuration

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Configuration Remarks ..............................27 LR DEVICE: Configure the device ......................32 LR DEVICE: Configure IO-Link devices ....................41 Profinet: Configure the device ........................43 Profinet: Configure IO-Link devices ......................49 Profinet: Programmers' notes .........................50...
  • Page 27: Remarks

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Remarks Supported configuration options ......................28 Connection possibilities ..........................28 Offline parameter setting ........................31 VPN connection ............................31 22369...
  • Page 28: Supported Configuration Options

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.1.1 Supported configuration options 22408 The AL1100 can be configured using the following options:  Parameter setting software LR DEVICE (version 1.0.x or higher) (art. no.: QA0011/QA0012) ...
  • Page 29 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Operation with Profinet connection (without LR DEVICE) 7396 Operation of the IO master as Profinet IO device. As an option, several IO-Link masters can be coupled via the Ethernet interfaces X21 and X22.
  • Page 30 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Operation with Profinet connection and LR DEVICE/LR SmartObserver 7398 The AL1100 can be connected via the two Ethernet interfaces X21 and X22 simultaneously with the Profinet control level (PLC) and the IT infrastructure level (monitoring/parameter setting).
  • Page 31: Offline Parameter Setting

    22762 An active VPN connection blocks the access of the parameter setting software LR DEVICE to the Profinet interface of the AL1100. ► Deactivate the VPN connection in order to be able to access the AL1100 with the LR DEVICE.
  • Page 32: Lr Device: Configure The Device

    Reset IO-Link master to factory settings ....................40 22402 The IO-Link master and the IO-Link devices connected to the AL1100 can be configured with the ifm software LR DEVICE. Further information about operation and functions of the LR DEVICE parameter setting software: ►...
  • Page 33: Set-Up

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.1 Set-up 12759 Factory settings On delivery, the AL1100 is configured with the → (→ p. 60) Before configuration with the LR DEVICE parameter setting software, the user must put the device into operation.
  • Page 34: Configure Communication Profile

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.2 Configure communication profile 22061 In order to copy the access rights to the device: ► Select the [LineRecorder] menu. >...
  • Page 35: Configure The Ethernet Interface

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.3 Configure the Ethernet interface 22404 To set the parameters of the Profinet interface (X21/X22): ► Select the [Network] menu. >...
  • Page 36: Configure The Interface To The Smartobserver

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.4 Configure the interface to the SmartObserver 12743 In order to set the parameters of the interface to the SmartObserver: ► Select the [LineRecorder] menu.
  • Page 37: Set The Operating Mode Of The Io-Link Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.5 Set the operating mode of the IO-Link ports 8714 The IO-Link ports X01...X04 of the device support the following operating types: ...
  • Page 38: Set Device Validation And Data Storage

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.6 Set device validation and data storage 7165 In operating mode "IO-Link" the user can set the behaviour of the IO-Link ports regarding device validation and backup/restore of parameter data of the connected IO-Link devices.
  • Page 39 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Name Description Possible values  Type compatible IO-Link device is compatible with V1.1 device with the V1.1 IO-Link standard Restore  Verification whether it is an...
  • Page 40: Reset Io-Link Master To Factory Settings

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.2.7 Reset IO-Link master to factory settings 12740 Factory settings When resetting the AL1100, all parameters are reset to the →...
  • Page 41: Lr Device: Configure Io-Link Devices

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > LR DEVICE: Configure IO-Link devices 22403 In order to configure the IO-Link devices connected to the AL1100 using the parameter setting...
  • Page 42: Offline Parameter Setting: Add Io-Link Devices Manually

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.3.1 Offline parameter setting: Add IO-Link devices manually 22817 The AL1100 supports the automatic recognition of IO-Link devices that are connected to the IO-Link interfaces.
  • Page 43: Profinet: Configure The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Profinet: Configure the device Install GSD file ............................44 Add the device to the Profinet network ....................45 Configure communication profile ......................47 Configure IO-Link ports ..........................48 Configure the Profinet interface ......................49...
  • Page 44: Install Gsd File

    Install GSD file 22410 To represent the AL1100 in a field bus projection software (e.g. STEP 7), ifm provides a GSD file. The user can download the GSD file from the ifm website (→ the GSD file, all parameters, process data, and their valid value ranges are defined.
  • Page 45: Add The Device To The Profinet Network

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.2 Add the device to the Profinet network 22406 The configuration of the Profinet parameters is done via the Profinet projection software.
  • Page 46 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration Add IO-Link ports ► Move the [4 Ports] node via drag&drop from the hardware catalogue to slot 1 of the AL1100. > Step 7 shows available IO-Link interfaces. ► Save the project.
  • Page 47: Configure Communication Profile

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.3 Configure communication profile 22760 In order to configure the access rights to the device: Open device editor ► Open STEP-7 application "HW Konfig".
  • Page 48: Configure Io-Link Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.4 Configure IO-Link ports 22759 In STEP 7, the following assignment of the Profinet slots to the IO-Link ports of the device applies:...
  • Page 49: Configure The Profinet Interface

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.4.5 Configure the Profinet interface 22761 In order to configure the Ethernet interface of the AL1100: Prerequisites > AL1100 is correctly integrated in the Profinet project (→...
  • Page 50: Profinet: Programmers' Notes

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > Profinet: Programmers' notes 12761 The programmer can access on the following data from the PLC application:  Read device information of the AL1100 ...
  • Page 51: Detect Diagnostics And Alarms

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Configuration > 8.6.2 Detect diagnostics and alarms 2272 Symbol / Meaning Remarks operational block I/O_FLT1 / Diagnostic alarms OB82 I/O_FLT2 / Pull/plug in alarms...
  • Page 52: Operation

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation Operation Identify device ............................53 Read device information .........................53 Reboot the device ...........................56 Error detection and elimination .......................56 Firmware update .............................57 Exchange IO-Link device........................58...
  • Page 53: Identify Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Identify device 22816 In the online mode, the user can identify the device using the status LEDs RDY, BF und SF ►...
  • Page 54: Web Interface: Read Device And Diagnostic Information

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > 9.2.1 Web interface: Read device and diagnostic information 12744 In order to read the diagnostic information about the current device status via the web interface: ►...
  • Page 55: Lr Device: Read Device Information

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > 9.2.2 LR DEVICE: Read device information 11614 To show information about the AL1100: ► Start LR DEVICE. ► Scan network for devices.
  • Page 56: Reboot The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Reboot the device 12760 When restarting the device, all settings are kept. To restart the AL1100: ► Start LR DEVICE. ► Scan the network for devices.
  • Page 57: Firmware Update

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Firmware update 22425 The new firmware is installed via the device's web interface. If the firmware update is not successful, deactivate all connections to the Profinet PLC, LR SmartObserver and LR DEVICE and repeat the process.
  • Page 58: Exchange Io-Link Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Operation > Exchange IO-Link device 7775 To exchange an IO-Link device: Requirement: > IO-Link device is with factory settings. > IO-Link device supports IO-Link standard 1.1 or higher.
  • Page 59: Maintenance

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Maintenance Maintenance 21577 The operation of the unit is maintenance-free. ► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this! ►...
  • Page 60: Factory Settings

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Factory settings Factory settings 22671 In the factory settings, the device has the following parameter settings: Parameters Factory setting [IP address] 0.0.0.0 [Subnet mask] 0.0.0.0...
  • Page 61: Appendix

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix Appendix Technical data ............................62 Profinet ..............................66 7156...
  • Page 62: Technical Data

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.1 Technical data Application ..............................63 Electrical data ............................63 Inputs / outputs ............................63 Inputs ..............................63 Outputs ..............................63 Interfaces ..............................64 Operating conditions ..........................64 Approvals / tests .............................64...
  • Page 63: Application

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.1.1 Application 23710 Application Application I/O modules for field applications Daisy-chain function Communication interface > 12.1.2 Electrical data 22819 Electrical data Operating voltage 20...30 DC;...
  • Page 64: Interfaces

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix 12.1.6 Interfaces 22822 Interfaces Communication interface Ethernet; IO-Link Communication interface IO-Link; TCP/IP; PROFINET IO Ethernet Transmission standard 10Base-T; 100Base-TX Transmission rate 10; 100 Protocol TCP/IP;...
  • Page 65: Mechanical Data

    Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.1.9 Mechanical data 22825 Mechanical data Weight [g] Materials Housing: PA; socket: brass nickel-plated > 12.1.10 Electrical connection 22826 Voltage supply IN X31...
  • Page 66 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2 Profinet Parameter data ............................67 Cyclic data ..............................70 Acyclic data ............................73 22433...
  • Page 67 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.1 Parameter data 22786 Slot Sub-slot Name Description Parameter of the IO-Link master Master Parameter data of the IO-Link master (→...
  • Page 68 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Parameters of the IO-Link ports 22787 Parameter Description Possible values [Fail-safe mode] Behaviour in case the Profinet No Fail Safe deactivated...
  • Page 69 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix Parameter Description Possible values  Type compatible V1.1 IO-Link device is compatible with device with Restore the V1.1 IO-Link standard  Verification whether it is an IO-Link...
  • Page 70 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.2 Cyclic data Profinet modules .............................71 PQI (Port Qualifier Information) ......................72 22429...
  • Page 71 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Profinet modules 22685 Module Description IO-Link 32 I/ 32 O + PQI 32 bytes input and output data and PQI IO-Link 16 I/ 16 O + PQI...
  • Page 72 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > PQI (Port Qualifier Information) 22686 Port Qualifier Information (PQI) contains diagnostic information about the IO-Link port. In addition to the process data, the IO-Link master sends the PQI to the Profinet controller.
  • Page 73 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > 12.2.3 Acyclic data 22427 > I&M datasets 22778 The AL1100 supports the following I&M datasets (I&M = Identification & Maintenance): >...
  • Page 74 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > I&M3 (Slot 0) 22781 Variable Description Access* Size Descriptor Description of the device (ASCII, padded with spaces) * ... r/w = read and write >...
  • Page 75 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-08-18 Appendix > Diagnostic and alarms 22784 Name Description Type code 0x02 EVNT_CODE_M_PDU_CHECK Receive frame with CRC error Alarm 0x1B EVNT_CODE_S_RETRY Repetitions detected Alarm...
  • Page 76 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-04-21 Index Inputs / outputs ..................65 Index Install GSD file ..................45 Interfaces ....................66 IO-Link ....................14 IO-Link circuits ..................20 Acyclic data .................... 75 IO-Link ports ..................
  • Page 77 Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100) 2017-04-21 Index Required background knowledge ............9 Reset IO-Link master to factory settings ..........41 Safety instructions ................... 8 Safety symbols on the device ..............10 Set device validation and data storage ..........
  • Page 79 Pte. Ltd • 47100 Puchong Selangor • Tel. +603 8063 9522 ifm efector S. de R. L. de C. V. • Monterrey, N. L. 64630 • Tel. +52 81 8040-3535 Sivilingeniør J. F. Knudtzen A/S • 1396 Billingstad • Tel. +47 66 / 98 33 50 ifm elctronic (pty) Ltd •...