Wiring Specifications; Field Electrical Wiring (Power Wiring Specifications) - Mitsubishi Electric PUHZ-RP200YKAR1 Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-RP200YKAR1:
Table of Contents

Advertisement

9

WIRING SPECIFICATIONS

9-1. FIELD ELECTRICAL WIRING (power wiring specifications)

Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity Main switch (Breaker)
Outdoor unit power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1.
A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2.
(RP35-140)
Max. 45 m
2
If 2.5 mm
used, Max. 50 m
2
If 2.5 mm
used and S3 separated, Max. 80 m
(RP200, 250)
Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50 m Total Max. for PEA. Wiring size 3 × 1.5 (Polar).
*3.
The 10 m wire is attached in the remote controller accessory.
*4.
The fi gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
Notes: 1. Wiring size must comply with the applicable local and national code. .
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
Power supply
A-Control
Outdoor Unit
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
1:1 system
Electrical wiring
Outdoor
unit
Unit
L
power
N
supply
S1
Earth leakage breaker
S2
wiring circuit breaker or
S3
isolating switch
RP35, 50V
~/N (single), 50 Hz,
~/N (single), 50 Hz,
230 V
*1
16 A
3 × Min. 1.5
*2
3 × 1.5 (Polar)
3 × 1.5 (Polar)
*2
1 × Min. 1.5
*3
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
*4
AC 230 V
*4
AC 230 V
*4
DC 24 V
*4
DC 12 V
Isolator
S1
S2
S3
Indoor
unit
1
Remote
controller
2
Indoor/outdoor
unit connection
cable
S1
S2
S3
RP60, 70V
RP100,125V
~/N (single), 50 Hz,
230 V
230 V
25 A
32 A
3 × Min. 2.5
3 × Min. 4
3 × 1.5 (Polar)
1 × Min. 1.5
1 × Min. 1.5
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
3 poles isolator
Synchronized twin and triple system Electrical wiring
• Synchronized twin
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
• Synchronized triple
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
26
RP140V
RP100, 125, 140Y
~/N (single), 50 Hz,
3N~ (3 ph 4-wires),
230 V
50 Hz, 400 V
40 A
16 A
3 × Min. 6
5 × Min. 1.5
3 × 1.5 (Polar)
3 × 1.5 (Polar)
1 × Min. 1.5
1 × Min. 1.5
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
S1
A-Control
S2
Indoor Unit
S3
Outdoor
Indoor
unit
unit
L
1
N
2
Indoor/outdoor
unit connection
cable
S1
S1
S2
S2
S3
S3
Outdoor
Indoor
unit
unit
L
1
Remote
controller
N
2
Indoor/outdoor
connection cable
S1
S1
S2
S2
S3
S3
RP200, 250
3N~ (3 ph 4-wires),
50 Hz, 400 V
32 A
5 × Min. 4
Cable length 50m:3×4 (Polar)/
Cable length 80m:3×6 (Polar)
1 × Min. 2.5
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Indoor
unit
1
Remote
controller
2
S1
S2
S3
Indoor
Indoor
unit
unit
1
1
2
2
S1
S1
S2
S2
S3
S3