SENSORS
Install the sensors inside the sensor holder. For this purpose, remove the cover from the end of
each sensor prior to insertion into the cable flange. Manually tighten the nuts of the cable flange.
Connect the BNC connectors of the sensors below the dosing pumps. Make sure that the
each pump ist equipped with the right sensor:
- pH (blue sensor) to the left, to the "pH" BNC connector
- Redox (yellow sensor) to the right, to the "Redox" BNC connector
The "Acid level" and "Chlorine level" BNC connectors must be connected to the tank alarm
floaters.
If the station is delivered with the sensors already installed in the circulation tank, make sure to
remove the cover or the receptacle filled with water, which serve to protect the sensors.
Turn on the filter and make sure that the water flows freely inside the analysis chamber.
When starting the dosing station, the following main menu will be shown (Ex) :
The two upper values stand for the water parameters. The percentage % below the
pH value indicates the quantity to be injected by the dosing pump. The indicated %
value is proportional to the maximum flow rate. The percentage % below the Redox value
indicates the proportional Redox regulation time controlled by the Control System.
PASSWORD
Access to the SETUP menu is protected by a four digit password.
The dosing station is delivered without password (0 0 0 0). It may be changed any time.
KEYBOARD
The keyboard consists of 4 arrow keys ! " # $ , the ESC and ENTER keys. In the main menu
(fig. 1), some keys have a double function. For example, if you press the # key for 4 seconds,
the dosing station will be shut off and OFF appears on the screen. Repeat the preceding
procedure to go back to normal operation.
Hit the ! key for the manual operation of the acid product pump. If you press the " key, the
manual operation of the chlorine pump will be available. In the programming mode, the REGUL
SYSTEM will automatically go back to screen 1, unless
you hit a key.

PUTTING INTO OPERATION

The sensors will deteriorate rapidly, if not
preserved in water. Therefore do not remove
the sensors from their protective cover, unless
you want to start the dosing station or the
sensor holder is filled with water.
7 .24 pH
Screen 1
WARNING
DISPLAY
650 mV
00 %
10 %
8