Alsvs Configuration - ABB Relion 650 Series Communication Protocol Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 415-UEN Rev. F
Section 6
6.1

ALSVS Configuration

The configuration of ALSVS is done automatically when the receiving of sampled data is defined in
the IED.
This configuration is done in ECT and there it is a column to fill in the SvCBRef. This field is used to
identify what sampled value stream that is supervised and should, according to IEC 61850, be set to
the IED and control block name of the sending IED. However, this is not used for the actual
communication and can be set to any string.
The identification of ALSVS supervised sampled value data stream is done with the SvCBRef setting
and not the instance number of the ALSVS instances.
IEC 61850 Edition 2, 650 series
Communication protocol manual
ALSVS Configuration
Configuration through SCL import is not supported.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 6
ALSVS Configuration
GUID-F4A2616F-3C43-4BB0-ABEF-C8FDAF454FBB v2