TCL TAC-07CHSA/XA71 Service Manual page 7

Wall mounted split-type air conditioners
Table of Contents

Advertisement

 
 
 
Electronic controller
NOTES:
RT-------Room Temperature.
IPT------Indoor Pipe Temperature.
ST------indoor Setting Temperature.
OPT---Outdoor Pipe Temperature.
CRT---Compensated Room Temperature
1. Automatic mode
1) The initial RT determines A/C working mode and the setting temperature (ST), the mode is
determined effective only once unless A/C shut-down and then re-started. If from other mode
switches to automatic mode (including mode conversion after shutdown), it should be that the
compress stop more than 3 min then temperature judgment and automatic mode are conducted (it
can conduct immediately from fan mode switched to automatic, the indoor fan stops, three minutes
later the response is made and start up). Within 3 min, the output as: Showing the room
temperature, indoor fans starts (or anti-cold airflow), the outdoor fan stops;
With auto re‐start controller, once being turned off or in case of an accidently power cut, the A/C is able  to 
retain and restore the original mode when being turned on or the power supply is resumed, if the  auto 
restart  function  activated.  power‐off  after  power‐on;  while  if  the  auto  restart  function  isn't  activated, 
the A/C enters standby state. 
Heat pump
Mode Initial
Cooling
Dry
Heating
Cooling-only
Mode Initial
Cooling
Dry
Ventilating
Under automatic mode (including from automatic converted into Dry mode), when A/C received the
temperature UP or DOWN signals from the remote controller, the setting temperature (ST) adjusts
correspondingly to the current room temperature plus or minus 1°C, the automatic regulating
temperature range is ± 2°C.
2. Cooling mode
1) The control of the compressor
a. When RT-ST≥1°C,the compressor is running.
b. When RT-ST<-1°C,the compressor stops.
c. When-1°C≤RT-ST<1°C, the compressor keeps its original state.
2) Outdoor fan motor and the compressor run simultaneously (except for defrosting).
3) The control of indoor fan motor:
a. Indoor fan motor can operate by automatic, low, middle, or high airflow speed circularly.
 
 
 
 
Air Conditioner Service Manual
RT
RT≥26°C
26°C>RT≥20°C
RT<20°C
RT
RT≥26°C
26°C>RT≥20°C
RT<20°C
Initial ST
23°C
7°C
23°C
Initial ST
23°C
7°C