3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of
the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size: "GAS VENT DIRECTLY BELOW, KEEP CLEAR OF
ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equip-
ment shall not approve the installation unless, upon inspection, the inspector observes carbon monox-
ide detectors and signage installed in accordance with the provisions of 248 CMR 5.08 (2)
(a)1 through 4.
[b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required to be
Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or struc-
ture separate from the dwelling, building or structure used in whole or in part for residential purposes.
[c) MANUFACTURER REQUIREMENTS- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When
the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting
system design or venting system components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system compo-
nents; and
2.A complete parts list for the venting system design or venting system.
[d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved sidewall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but identifies "special venting systems", the following
requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equip-
ment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation instructions.
[ e) A copy of all installation instructions for all Product Approval side wall horizontally vented gas
fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design
instructions shall remain with the appliance or equipment at the completion of the installation.
77