3.3A.4. FIX THE UNIT
(1) Hang the unit
Hanger bolt
Nut A
(Field supply)
Washer
(Accessories)
Nut B
(Field supply)
Nut A
(Field supply)
Washer
(Accessories)
Nut B
(Field supply)
*: I t might become difficult to open and shut the Cover /control box cover when the
length exceeds 20mm.
(2) Leveling
Base horizontal direction leveling on top of the unit.
OK
Air
OK
• Leave a space of 100 mm or more between the inlet port and the ceiling.
• Fasten the unit securely with Special nuts A and B.
En-5
Hanger
Hanger bolt
Hanger
Unit
20mm
length
Cover
Ceiling
Level
NO GOOD
Level
NO GOOD
CAUTION
3.3B. Install the unit (Wall mounted type/ Floor standing
concealed type)
• Install the air conditioner in a location which can withstand a load do at least 5
times the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
• If the job is done with the panel frame only, there is a risk that the unit will come
loose. Please take care.
3.3B.1. UNIT INSTALLATION EXAMPLE
(Wall mounted type/Floor standing concealed type)
Connect the locally purchased duct.
(1) Inlet side
• Connect the duct to the locally purchased inlet flange.
• Connect the flange to the body with the locally purchased tapping screws.
• Wind the inlet flange connecting to the duct with the aluminum tape etc. to avoid the
air leakage.
• When the duct is connected to inlet side, remove contained filter and surely attach
locally purchased filter at inlet opening.
(2) Outlet side
• Connect the duct with adjusting inside of outlet flange.
• Wind the outlet flange connecting to the duct with the aluminum tape etc. to avoid the
air discharge.
• Insulate the duct to avoid the dew condensation.
• Check that duct work does not exceed the range of external static pressure of
equipment.
• Make sure to insulate ducts to avoid the dew condensation.
• Make sure to insulate between ducts and walls if metal ducts are used.
• Please explain handling and washing methods of locally purchased materials to the
customer.
• To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
• When connecting the duct to the outlet port of the indoor unit, be sure to insulate the
outlet port and the installation screws to prevent water from leaking around the port.
• Set the static pressure outside the unit to 90 Pa or less (the allowable range is
between 0 and 90 Pa).
• Remove the screws, and then remove cover and fan guard.
• Install the cover with the screws as shown in the illustration below.
Model
7000,9000,12000,14000 BTU/h
18000 BTU/h
WARNING
CAUTION
CAUTION
Screw
M5
9
11
screw (M5)
Cover
Fan guard