7. REMOTE CONTROLLER SETTING

.
When detecting the room temperature using the remote con-
troller, please set up the remote controller according to the
following conditions. If the remote controller is not located prop-
erly, the correct room temperature will not be detected, and
thus abnormal conditions like "not cooled" or "not heated" will
occur even if the air-conditioner is running normally.
• Locate where an average temperature for the room being
air conditioned will be sensed.
• Do not locate directly exposed to the outlet air from the
air-conditioner.
• Locate out of direct sunlight.
• Locate away from the influence of other heat sources.
Do not touch the remote controller PC board and PC board parts directly with your hands.
Do not wire the remote controller cable together with or parallel to the connection ca-
bles, and power supply cable of the INDOOR UNIT and OUTDOOR UNIT, BRANCH
BOX. It may cause erroneous operation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire.
Do not set the DIP switches, either on the air conditioner or the remote controller, in any
way other than indicated in this manual that is supplied with the air conditioner. Doing
so may result in improper operation.

7.1. Installing the remote controller

Open the operation panel on the front of the remote controller, remove the 2 screws indi-
cated in the following figure, and then remove the front case of the remote controller.
When installing the remote controller, remove the connector from the front case. The
wires may break if the connector is not removed and the front case hangs down.
When installing the front case, connect the connector to the front case.
Front case
(back side)
SET BACK
Screws
Connector
When remote controller cable is concealed
(1) Conceal the remote controller cable.
(2) Pass the remote controller cable through the hole in the rear case and connect the
remote controller cable to the remote controller terminal board specified in figure.
(3) Clamp the remote controller cable sheath with the binder as shown in figure.
(4) Cut off the excess binder.
(5) Install the rear case to the wall, box, etc., with 2 screws figure.
1. Red
2. White
Hole
3. Black
Binder
(Small)
When connecting the remote controller
wires, do not overtighten the screws.
[Example]
Remote
controller cable
Box
Rear case
Ground the remote controller if it has a ground wire.
CAUTION
Temperature
sensor
Rear case
CAUTION
Connector
Screws
Wrap the connector and remote
controller wires with vinyl tape
or some other type of insulation
as shown in the figure.
Remote controller
120
30
Hole
Install the remote controller wires so as not to be direct touched with your hand.
Do not touch the remote controller PC board and PC board parts directly with your
hands.

7.2. Setting the dip switches

Set the remote controller DIP switches.
[Example]
Front case (back side)
DIP switch 1
SW state
NO.
OFF
ON
1
2
3
DIP-
4
switch 1
5
6
★ Invalidity
Validity
17
33.5
23
8
4.5
6
Hole × 2
Hole × 3
CAUTION
OFF
ON
1
2
3
4
5
6
ON
Detail
Cannot be used.
(Do not change)
Dual remote controller setting
* R efer to 2. DUAL REMOTE CONTROL-
LERS in 7.5. Special Installation Methods.
Cannot be used.
(Do not change)
Cannot be used.
(Do not change)
Cannot be used.
(Do not change)
Memory backup setting
* S et to ON to use batteries for the memory
backup. If batteries are not used, all of the
settings stored in memory will be deleted if
there is a power failure.
(★ Factory setting)
Unit: mm