Chapter 10 Communications
10.5.6 Modbus Multi-Drop Mode
A maximum of 32 nodes (1 controller, 31 responders) are supported in a multi-drop installation.
10.5.7 Modbus Protocol
Authoritative information on the Modbus protocol can be found at www.modbus.org.
Supported baud rates are 9600 and 19200 with 9600 as the default (none parity, 1 stop bit) and follower addresses
set as 1 by default.
Status reading and configuration of important parameters (adjustable with Honeywell Fixed Platform App and HART)
can also be performed using the Modbus interface. This appendix describes only how to monitor Searchline Excel Plus &
Searchline Excel Edge status using Modbus.
10.5.8 Modbus Registers
Modbus Holding Register
Address
First
Last
Qty
40001
40001
1
40002
40002
1
40003
40004
2
40005
40005
1
40006
40006
1
40007
40007
1
40008
40008
1
40009
40009
1
40010
40010
1
40011
40011
1
40012
40014
3
40015
40015
1
40016
40016
1
40017
40017
1
40018
40030
13
40031
40035
5
40036
40036
1
40037
40038
2
40039
40039
1
40040
40040
1
40041
40041
1
40042
40042
1
40043
40043
1
40044
40044
1
40045
40045
1
40046
40046
1
40047
40047
1
40048
40052
5
40053
40059
7
40060
40060
1
40061
40061
1
Register
Parameter Description
Type
r
Modbus responder address
r
Detector Id
r
Gas reading
r
Reserved
r
Detector detail status
r
Operating state
r
Heart Beat
r
Discrete or proportional
r
Alarm Latch config
r
Measurement unit
r
Relay status(Active/Inactive)
r
ADC Temp. Sensor
r
PSU1 Temp. Sensor
r
AFE Temp. Sensor
r
Device Name
r
Reserved
r
Sensor type
r
mA Output
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Voltage monitor
r
Reserved
r
Reserved
r
Voltage monitor
r
Configuration counter
Searchline Excel™ Plus / Searchline Excel™ Edge – Technical Manual
Additional Description
MSB -> 0x28
LSB -> Responder address (1 to 247,
address 60 excluded)
Identical to 40001
Reported gas concentration
------
*see notes
*see notes
low 16 bits of SDS variable
0=discrete, 1=proportional
mask of individual alarm latches
------
0=deenergized, 1=energized
------
------
------
From Bluetooth
------
------
mA Output readback current
24V_PROT_SW
5V0_SAFE
12V_SAFE
3V3_SAFE
12V
3V3
5V0
1V2_SAFE
+5V_HTR
------
------
+INTRA_1V2
From HART
Notes
Note 5
Note 5
Note 13
Note 3
Note 8
Note 4
Note 16
Note 15
Note 17
Note 17
Note 17
Note 17
Note 17
Note 17
Note 17
Note 17
Note 17
Note 17