Fujitsu WATERSTAGE WOYG160LJL Maintenance Document page 6

Air to water heat pump split single service and integrated dhw type
Hide thumbs Also See for WATERSTAGE WOYG160LJL:
Table of Contents

Advertisement

Outdoor unit
Error number
LED 2 (green)
11
1 Flash
23
2 Flashs
31
3 Flashs
32
3 Flashs
41
4 Flashes
42
4 Flashes
61
6 Flashs
62
6 Flashs
63
6 Flashes
64
6 Flashes
65
6 Flashs
67
6 Flashs
68
6 Flashs
71
7 Flashes
72
7 Flashes
73
7 Flashes
74
7 Flashes
77
7 Flashs
78
7 Flashes
84
8 Flashes
86
8 Flashes
94
9 Flashes
95
9 Flashes
97
9 Flashes
98
9 Flashes
A1
10 Flashes
A3
10 Flashes
A4
10 Flashs
A5
10 Flashes
A9
10 Flashs
Continuous fl ashing
-
(1 sec On / 1 sec Off )
Continuous
-
lighting
DIP SW
Interface Board
fi g. 1 - Location of DIP switches and diodes on the
hydraulic unit interface card
- 6 -
LED display
Error contents
LED 1 (red)
1 Flash
Communication error between Hydraulic unit and Outdoor unit
3 Flashs
Connection forbidden (series error)
1 Flash
Indoor unit power supply abnormal
2 Flashs
Serial communication error between Controller /Interface PCBs
1 Flash
Heat pump capacity signal error (Open or short)
2 Flashes
Hydraulic unit heat-exchange thermistor Error
1 Flash
Outdoor unit power supply abnormal
2 Flashs
Outdoor unit main PCB error
3 Flashes
Inverter error
4 Flashes
Active fi lter error
5 Flashs
Outdoor unit IPM error
7 Flashs
Outdoor unit power short interruption error (protective operation)
8 Flashs
Outdoor unit magnetic relay error
1 Flash
Discharge thermistor error
2 Flashes
Compressor thermistor error
3 Flashes
Heat-exchange thermistor (outlet / intermediate) error
4 Flashes
Outdoor thermistor error
7 Flashs
Outdoor unit heat sink temp. thermistor error
8 Flashes
Expansion valve thermistor error
4 Flashes
Current sensor error
6 Flashes
Pressure sensor error / Pressure switch error
4 Flashes
Current trip
5 Flashes
Detection of compressor position error / Compressor start up error
7 Flashes
Outdoor unit fan1 motor error
8 Flashes
Outdoor unit fan2 motor error
1 Flash
Discharge temperature protection
3 Flashes
Compressor temperature protection
4 Flashs
Outdoor unit pressure error
5 Flashes
Low pressure abnormal
9 Flashs
Current overload error
Pump down operation
Off
Defrosting
LED2
(Green)
LED1
(Red)
Waterstage / Maintenance Manual / 2105 - EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents