Remove the COMP BOLTs.
(4 places)
Cut the Discharge pipe in this range.
Caution
Keep their shape better.
There is a possibility of catching fire to oil when removing by the welding without cutting it.
Procedure for compressor installation.
Reverse procedure to removing the compressor.
Precautions for installation of Compressor.
(1) When brazing, do not apply the fl ame to the terminal.
(2) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Waterstage / Maintenance Manual / 2105 - EN
Discharge side
Range
Cut the injection pipe.
Cut the Suction pipe in this range.
Remove the Compressor.
Suction side
Range