Compressor Removal - Fujitsu WATERSTAGE WOYG160LJL Maintenance Document

Air to water heat pump split single service and integrated dhw type
Hide thumbs Also See for WATERSTAGE WOYG160LJL:
Table of Contents

Advertisement

▼ Compressor removal

Precautions for exchange of Compressor.
Do not allow moisture or debris to get inside refrigerant pipes during work.
Procedure for compressor removal.
(1) Turn off power.
(2) Remove the SERVICE PANEL and PIPE COVER FRONT.
(3) Fully open the 3WAY VALVE(Gas) and 3WAY VALVE(Liquid).
(4) Open the EEVs of Outdoor units and Indoor units by vaccuming mode.
(5) Collect the refrigerant from the 3WAY VALVE.
Start the following work after completely collecting the refrigerant.
Do not reuse the refrigerant that has been collected.
Screws
VALVE PLATE
Remove the 6 mounting screws.
Waterstage / Maintenance Manual / 2105 - EN
Screws
Screws
Remove the VALVE PLATE.
- 131 -

Hide quick links:

Advertisement

Table of Contents
loading