11.6 Vertical Airflow Direction Control

11.6.1
Auto Control
(Cooling Operation Condition)
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will
stop swinging.
(Heating Operation Condition)
When the piping air temperature reaches 38°C, the louver is changed from upper to lower limit. When the piping
air temperature falls 35°C, the louver is changed from lower to upper limit.
Closing
position
22°
/ 148°
Lower limit for cooling mode/39°
Closing
position
35°
/ 148°
Lower limit for heating mode/52°
32
Horizontal
Upper limit for cooling
mode/17°
Swing up and down
Horizontal
Upper limit/17°