Climate menu (Temperature) ............................. 14 4.3.2 Scene Menu ..................................15 4.3.3 Light menu ................................... 15 RGB(W) Color picker / Color temperature picker ......................... 17 4.4.1 Shading menu ..................................18 4.4.2 Monitoring Menu ................................19 4.4.3 Configuration menu ................................20 Seite 3 Thermokon Sensortechnik GmbH...
Page 4
Unicode character table (UTF-16) ..................50 Modbus Protocol ......................51 Supported Control Commands ..............................51 Data Transmission ..................................51 9.2.1 Master/Slave Protocol ................................ 51 9.2.2 Data Frame ..................................51 9.2.3 Transmission Mode RTU ..............................52 Seite 4 Thermokon Sensortechnik GmbH...
Information about the responsible contact person can be obtained at any time by telephone or e-mail. You may also visit our website for contact details: https://www.thermokon.de/en/contact/contact-persons/ We appreciate your contributions, feedback and user experiences in order to constantly improve our products! Seite 5 Thermokon Sensortechnik GmbH...
2 Description of product features The Thermokon room control units (NOVOS family and thanos EVO) combine all relevant room functionalities for an intelligent room control in one device, such as temperature control or control of fans, luminaires, blinds or screens. Additionally, depending on the device configuration, up to four sensors can be integrated (CO2, VOC, temperature, humidity) to maintain a comfortable room climate throughout.
Each device that communicates through Modbus is assigned a unique address. In serial networks, only the node assigned as the Master may execute a command. The BUS interface can be parameterized by means of the NOVOSapp or using the onboard screen configuration menu. NOVOS 7 NOVOS Touch / thanos EVO Bus address 1-247 (Address 1 –...
Display and operating elements The NOVOS 7 has an intuitive user interface using a rotary/press encoder and four capacitive keys below the screen. NOVOS Touch and thanos EVO have a high-resolution full-touch display, which is used for operating and navigating through the menus. Both devices use a structured and language- neutral graphical user interface.
The room occupancy and ECO function are triggered on the device via toggle button. ▪ Maintenance due NOVOS 7: Depending on the configuration, switching to ECO mode is conducted either in the ▫ Coil 27 respective submenu (carousel), in the On = 1 | Off = 0 temperature menu or through a favorite button.
Second; Data address 1111 DD.MM.YYY. Configuration data block „Display“ ▪ Screensaver ▫ Data address 1207 NOVOS 7 NOVOS Touch / thanos EVO 0 = Off 1 = Date/ Time 2 = individual graphic ▪ Display of an own logo (binary coded) 4.2.3...
210 = 21,0 °C ▪ Set point adjustment range ▫ Data address 1303 30 = ±3,0K ▪ Set point adjustment step width ▫ Data address 1304 1-50 = ±0,1K - ±5,0K NOVOS 7 NOVOS Touch / thanos EVO Seite 11 Thermokon Sensortechnik GmbH...
22 = Menu Scenes NOVOS 7 23 = Menu Monitoring 24 = Menu Fan control (NOVOS 7) Favorite buttons NOVOS Touch / thanos EVO If only one favorite button in the home screen is required, address 1117 (button 1) must be written. If...
Data address 1122 NOVOS 7 Carousel (main menu) 0 = no By turning the encoder, the NOVOS 7 switches to the 1 = yes main menu (carousel). The menu is still operated by the rotary/press encoder. All functions i.e. symbols (except the settings menu) can be activated or Configuration data block „Display“...
0 = absolute | 1 = relative to adjust the set point and fan stages. ▪ Base set point NOVOS 7 climate menu ▫ Data address 1302 The operation of the menu is intuitively lead by using 210 = 21,0 °C the rotary/push button.
In the Scene menu, up to eight scenes can be configured individually. Scenes can be activated or deactivated using ▫ Data address 1801 the rotary/push button (NOVOS 7) or the touch display (NOVOS Touch). Scene groups ▪ Selection the icon for scenes Buttons for up to eight different scenes can be ▫...
Page 16
User key lock (AUTO mode, Data address 208 | Coil 32-39) With NOVOS 7, Touch and Thanos EVO, the keys of the individual lighting circuits can be blocked by the BMS. All locked keys of the respective lighting group are greyed out in the entire user interface and cannot be operated by the user.
Min. light color 7; Data address 1559 ▫ Max light color 7; Data address 1560 ▫ Min. light color 8; Data address 1561 ▫ Max light color 8; Data address 1562 Min. value 1000-6600K Max. value 6600-15000K Seite 17 Thermokon Sensortechnik GmbH...
Just like the lighting groups, up to eight shading Representation in the room plan = 1 circuits can be controlled. The shading menu is Display both= 2 available in the NOVOS 7, NOVOS Touch as well as ▪ thanos EVO. Selection of the shading icons ▫...
Parity Even ▫ Beschattung 6; Datenadresse 1720 ▫ 1 Stop bit The password for NOVOS 7 / Touch and thanos EVO ▫ Beschattung 7; Datenadresse 1741 is “2030” and is set initially as a default factory ▫ Beschattung 8; Datenadresse 1762 setting.
Zeit nach der Datenadresse 197 zurückgesetzt wird. 0 deaktiviert die Rückstellzeit nach erkannter Rückstellzeit – Datenadresse 197 r / w ● 4008 Interaktion muss in diesem Fall von der GLT uint16_t zurückgeschrieben werden. Wert in Sekunden Seite 21 Thermokon Sensortechnik GmbH...
If the operator has selected the Auto Fan Mode (104=6), the exact fan level can be additionally displayed with the higher-level control. Exception: With NOVOS 7, only the designation AUTO is displayed for parameter 7-12 in the fan menu. Attention: With NOVOS 5, only the AutoStages(6..12) can be...
/ w Green value 0..255 ● (according to setting, Data uint16_t address 1542) r / w Blue value 0..255 ● uint16_t Lighting 8 r / w White value 0..255 ● uint16_t Seite 23 Thermokon Sensortechnik GmbH...
● ● ● uint16_t Bit 1 = Temp Bit 2 = VOC Bit 3 = CO2 Connection to terminal 7 Status of digital input 0 = open ● ● ● ● uint16_t 1 = closed Seite 26 Thermokon Sensortechnik GmbH...
Factory default setting 0 = Calibration deactivated (Icon not active after countdown expire, at r / w Calibration interval ● ● ● ● 1116 value >0, icon active after countdown uint16_t expire) 0 … 48 Months Seite 28 Thermokon Sensortechnik GmbH...
Page 29
Home screen. The favourite button is directly linked to the linked function menu. The assignment of favourite buttons for NOVOS 7 / Touch and Thanos EVO is explained in detail in the corresponding data sheets. 0 = no function...
10 = 1,0 Display ECO button (menu bar and temperature menu) 0 = no 1 = yes ECO button r / w Only NOVOS 7: 2 = yes, climate ◌ ● ● 1305 (Display ON/OFF) menu and carousel In ECO mode, users cannot adjust the setpoint and fan stage.
Page 32
Select, which value should be displayed in the home screen. Bit 0: Display actual temperature Value display on home screen ● ● r / w 1313 Bit 1: Display setpoint Value = 0 -= OFF Value = 1 -= ON Seite 32 Thermokon Sensortechnik GmbH...
Unicode format per register Lighting 1 – Icon Selection of the icon for Lighting 1 0 = Universal light bulb ● ● r / w 1415 1 = Spot 2 = Light-cassette 3 = Floor lamp Seite 33 Thermokon Sensortechnik GmbH...
Page 34
1547 -1562. 0 = Slider 1 = Push button operation 2 = Push button operation (raw) 3 = RYB Color picker color circle + dimmer slider) 4 = Color temperature picker color circle + dimmer slider) Seite 34 Thermokon Sensortechnik GmbH...
Page 35
Description see Lighting 1 ● ● r / w 1472 Lighting 4 - Coordinate X Description see Lighting 1 ● r / w 1473 Lighting 4 - Coordinate Y Description see Lighting 1 ● r / w 1474 Seite 35 Thermokon Sensortechnik GmbH...
Page 36
Lighting 8 - temperature picker ● 1000 6600 r / w 1561 Min. Color temperature 1000-6600K Upper limit for the color Lighting 8 - temperature picker ● 6600 15000 r / w 1562 Max. Color temperture 6600-15000K Seite 36 Thermokon Sensortechnik GmbH...
Page 38
/ w 1663 up/Down step width Shading 3 - Coordinate X Description see Shading 1 ● r / w 1664 Shading 3 - Coordinate Y Description see Shading 1 ● r / w 1665 Seite 38 Thermokon Sensortechnik GmbH...
Page 39
/ w 1726 Up/Down - step width Shading 6 - Coordinate X Description see Shading 1 ● r / w 1727 Shading 6- Coordinate Y Description see Shading 1 ● r / w 1728 Seite 39 Thermokon Sensortechnik GmbH...
Page 40
/ w 1768 Up/Down – step width Shading 8 - Coordinate X Description see Shading 1 ● r / w 1769 Shading 8 - Coordinate Y Description see Shading 1 ● r / w 1770 Seite 40 Thermokon Sensortechnik GmbH...
Description see Scene 1 ● ● r / w 1892 Description Scene 8 Description see Scene 1 ● ● Scene 8 r / w 1893 Icon Scene 8 Description see Scene 1 ● ● r / w 1905 Seite 41 Thermokon Sensortechnik GmbH...
Overwrite external value 4 = Data address 3109 External Sensor 3 3009 ff. (3010-3024 / 3036-3049) Version ≥ 1.4 (NOVOS 7/Touch, thanos EVO) External value can also be set in register 508-511 External Sensor 4 3109 ff. (3110-3124 / 3136-3149) atm.
Page 43
Colour definition for the fourth range. Range 4 starts with threshold value 3- r / w Range 4 colour ● ● ● ● 2019 4 and ends with threshold value 4-5. uint16_t See Range 1 Seite 43 Thermokon Sensortechnik GmbH...
Page 44
Description for the sensor Max. 12 characters. One character in Sensor Text[6] 2043 Unicode format per register. Sensor Text[7] 2044 Sensor Text[8] 2045 Sensor Text[9] 2046 Sensor Text[10] 2047 Sensor Text[11] 2048 Display Number of decimal 2049 places Seite 44 Thermokon Sensortechnik GmbH...
Status Scene 7 0 = not active r / w ● ● 1 = active Coil for Scene ON / OFF Status Scene 8 0 = not active r / w ● ● 1 = active Seite 46 Thermokon Sensortechnik GmbH...
0 = not active r / w ● ● ● ● 1 = active Coil Register for icon ON / OFF Show Maintenance (Icon) 0 = not active r / w ● ● ● ● 1 = active Seite 47 Thermokon Sensortechnik GmbH...
AUTO-Mode Shading 7 0 = not active r / w ● 1 = active Coil for AUTO Mode ON / OFF AUTO-Mode Shading 8 0 = not active r / w ● 1 = active Seite 48 Thermokon Sensortechnik GmbH...
4 = Thursday bit 5 = Friday bit 6 = Saturday r / w Register address ● ● 32.767 6118 uint16_t r / w New register value ● ● 6119 -32.768 32.767 int16_t Seite 49 Thermokon Sensortechnik GmbH...
In general a MODBUS telegram starts with the address of a slave, followed by a control command (e.g. read register) and the data. By means of the checksum at the end of the telegram, the BUS participants can recognize transmission errors. Seite 51 Thermokon Sensortechnik GmbH...