Quest Controls TELSEC MP2x User Manual page 29

Table of Contents

Advertisement

Outputs Registers
Function Code
Read coil/output
(FC1)/(FC5)
(FC15) for write multiple
Control Registers
Function Code
Register
0
1
Holding Register
(FC3/FC6)
(FC16) for write
multiple
2
3
4
5
Rev 2.1 10/21/21
Register
0
1
2
3
Description
Read/Write
Slave Address
R/W
Baud Rate
R/W
Data Mode
R/W
Product ID
RO
Firmware
RO
Revision
Reset
WO
- 25 -
Description
Output 1 Status
Output 2 Status
Output 3 Status
Output 4 Status
Notes
1-247
Enumerated:
0 – 300, (not supported)
1 – 600, (not supported)
2 – 1200,
3 – 2400,
4 – 4800,
5 – 9600,
6 – 19200,
7 – 38400,
8 – 57600,
9 – 115200
Enumerated:
0 – 8N1,
1 – 8E1,
2 – 8O1,
3 – 8N2, (not supported)
4 – 8E2,
5 – 8O2
1
convert to hex to get
Kernel version and
Filesystem versions. Initial
build 1542 (hex 0606)
Must write 57005 to data
register for reset
TELSEC
Read/Write
Notes
RW
0 off, 1 on
Default 247
Default 9600
Default 8N1
©
MP2X User Guide

Advertisement

Table of Contents
loading

Related Products for Quest Controls TELSEC MP2x

Table of Contents