for Modbus, 9600 baud and 8-N-1 (these are the MP2 defaults). Press Save Settings and wait for
the system to restart.
3. Go to Program/Modbus (Port #) where # is the port number you just configured.
4. Create a new Device by clicking on the Add new device button. Enter the address of 247 and
give the device a name. Click on the Done button.
5. The new device will be added to the list. Click on the down arrow for the device and then the
Add new point button.
6. Enter a 4-character ID this is used for reference in the system. This value can be what every you
want. I.e. TMP1 for temporary 1 point. Enter a display name, function code will be 3- Holding
register, and then enter the register number and format (use Word). Press the Done button and
then Save Settings. Note the system will automatically save if you do not press the save button
within 120 seconds.