7. Repeat step 5 for any additional registers you want to change such as baud rate or data mode.
These settings typically don't need to be changed unless you have other devices on the Modbus
485 network that need to operate at different settings. Note: all devices must have the same
baud rate and data mode setting but have a unique address.
8. Go to Status/Modbus Status (Port #) where # = the port number used. The system should be
displaying the created point with the current value of 247 (the default address).
9.
Click on the write button and change the address to the desired value which will be stored in
non-volatile flash memory.
Rev 2.1 10/21/21
- 11 -
©
TELSEC
MP2X User Guide