3.7 Wiring Outputs

There are four form C relays available for control of external devices based upon alarm conditions or
time schedules. Place wire between the common and normally open or normally closed terminals for
each output on the MP2x. The relays are designed for Class 2 wiring and are rated for a maximum of 1
amp at 24VAC or 30VDC, 0.3 A @ 60VDC.
Figure 8 - Wiring Outputs

4 Local Operation

4.1 Power LED

®
Once the TELSEC
MP2x is installed and powered, the system will start operating. Under normal
operation the green Power LED will flash at one second intervals to indicate the system is operating
properly. Occasionally there may be a pause in this operation if the system is saving data to flash
memory. If the LED is off for longer than one minute, then check the power connection and cycle
power to the unit. If the LED is constantly on longer than a minute, then cycle power to the system to
see if it goes back to normal operation of flashing the LED.

4.2 Relay Outputs

The normally open/normally closed terminations on the unit refer to when the output is de-energized.
Outputs can be operated by sending Modbus RTU write commands to turn on/off the outputs. See the
register map in section for further details.

4.3 Restoring to Factory Defaults

®
The TELSEC
MP2x has a small access hole on the right side for the cold start switch. Holding this switch
in for approximately 15 seconds during a power up (cycle power off then back on) will cause the system
to erase all programmed settings and go back to the factory defaults. During the Cold Start process, you
©
Rev 2.1 10/21/21
- 8 -
TELSEC
MP2X User Guide