To read the inputs in Celsius as a floating-point number
Function Code
Input Register (FC4)
Rev 2.1 10/21/21
Register
Description
Input 1 tempC
160
Input 2 tempC
162
Input 3 tempC
164
Input 4 tempC
166
Input 5 tempC
168
Input 6 tempC
170
Input 7 tempC
172
Input 8 tempC
174
Input 9 tempC
176
Input 10 tempC
178
Input 11 tempC
180
Input 12 tempC
182
Input 13 tempC
184
Input 14 tempC
186
Input 15 tempC
188
Input 16 tempC
190
Input 17 tempC
192
Input 18 tempC
194
Input 19 tempC
196
Input 20 tempC
198
Input 21 tempC
200
Input 22 tempC
202
Input 23 tempC
204
Input 24 tempC
206
Input 25 tempC
208
Input 26 tempC
210
Input 27 tempC
212
Input 28 tempC
214
Input 29 tempC
216
Input 30 tempC
218
Input 31 tempC
220
Input 32 tempC
222