SERVICING
HIGH VOLTAGE
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRING.
F
SOURCES MAY BE PRESENT.
AILURE TO DO SO MAY CAUSE
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove blower compartment door to gain access to
the thermostat low voltage wires located at the furnace
integrated control module.
2. Remove the thermostat low voltage wires at the furnace
integrated control module terminals.
With Power On (and Door Interlock Switch closed):
WARNING
L
INE VOLTAGE NOW PRESENT
3. Use a voltmeter, check voltage across terminals R and
C. Must read 24 VAC.
4. No voltage indicates faulty transformer, open fuse, bad
wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line
voltage connections, fuse, splices, and blower door in-
terlock switch.
6. If line voltage is available to the primary side of trans-
former and not at secondary side, the transformer is
inoperative. Replace.
7. After completing check and/or replacement of trans-
former and check and/or repair of control circuit, rein-
stall blower compartment door.
8. Turn on electrical power and verify proper unit opera-
tion.
4-Wire ECM Motors
Description
These models utilize an Nidec US motors, 4-wire variable
speed ECM blower motor. The ECM blower motor provides
constant CFM.
The motor is a serially communicating variable speed motor.
Only four wires are required to control the motor: +Vdc,
Common, Receive, and Transmit.
The +Vdc and Common wires provide power to the motor's
low voltage control circuits. Typical supply voltage is 9-15
volts DC.
ECM Control Connections
ECM control connections are made through the integrated
ignition control. No other control connections are needed.
NOTE: An inductor (Factor Power Choke Correction) is
required when powering the 3/4 and 1 horsepower motors
with 115 volts (inductor pictured below). The operation of this
inductor is to reduce the line current by storing the electrical
energy in a magnetic field, such that the voltage AC waveform
leads the current AC waveform. In other words, the inductor
44
WARNING
M
ULTIPLE POWER
reduces line current which extends the life of the 3/4 and 1
horsepower motors.
IMPORTANT: If the inductor fails, there will be no motor
operation since this is the "LINE" power supply, black wire,
from the integrated ignition control to the motor. To determine
if the inductor is at fault, you can bypass by the inductor by
disconnecting the black wire from the inductor and connecting
it directly to the motor. If the motor operates then the inductor
will need to be replaced.
Checking ECM Motors
ECMmotors connect directly to the AC Line Voltage. DO NOT
insert contactors in series with the ECM Motor AC Line. The
control is powered continuously to insure reliable start-up.
The connector plug is polarized, verify and reverify correct
connector orientation before applying power. DO NOT force
plug into motor and make sure power is off before inserting
power connector. DO NOT apply voltage to terminals 1 or 2.
General Checks/Considerations
1. Check power supply to the furnace. Ensure power supply is
within the range specified on rating plate. See section S-1.
2. Check motor power harness. Ensure wires are continuous
and make good contact when seated in the connectors.
Repair or replace as needed.
3. Check motor control harness. Ensure wires are continuous
and make good contact when seated in the connectors.
Repair or replace as needed.
4. Check thermostat and thermostat wiring. Ensure
thermostat is providing proper cooling/heating/continuous
fan demands. Repair or replace as needed.
5. Check blower wheel. Confirm wheel is properly seated on
motor shaft. Set screw must be on shaft flat and torqued
to 165 in-lbs minimum. Confirm wheel has no broken or
loose blades. Repair or replace as needed.
6. Ensure motor and wheel turn freely. Check for interference
between wheel and housing or wheel and motor. Repair
or replace as needed.
7. Check housing for cracks and/or corrosion. Repair or
replace as needed.
8. Check motor mounting bracket. Ensure mounting bracket
is tightly secured to the housing. Ensure bracket is not
cracked or broken.
UltraCheck-EZ
Diagnostic Tool
TM
The UltraCheck-EZ
diaganostic tool is the preferred method
TM
(part # UTT-01) to diagnose the ECM motor.