6.2

Pump data

In this menu all pump relevant parameters are set . The menu has the following structure
6.2.1

Run-on time

In this menu the run-on time is set (in sec). The run-on time is the time period, during which the
pump(s) continue to run, after the level has fallen below the cut-out level. A value of 0000 deactivates
this function.
6.2.2
Pump run time limitation
The run time of the pumps can be limited to a max. adjustable run time. If the pump runs
uninterruptedly longer than the set time period, an alarm is given. In case of a dual pump control,
rotation of the pumps is additionally effected. A value of 0000 deactivates this function.
6.2.3

Pump rotation when using dual pump control

In this menu point, the behaviour of the control concerning pump rotation can be determined.
When entering a value of "0000", pump rotation is effected only after both pumps have been switched
off. If a value between "0001" and "9998" is entered, then pump rotation is effected after both pumps
have been switched off, at the latest after the set time period (in seconds) has elapsed.
Entering a value of "9999" deactivates the pump rotation function, that is the control starts basically
with pump 1 and pump 2 is always the peak load pump. Note: In the case of pump rotation function
(1/1) and a value of "9999", pump 2 is never switched on automatically!
HSK_operating_manual_English_Ver3.doc
Run-On Time
0003sec
Max. allowable
pump run time
0300sec
Load rotation
after 0300sec
Time Start Delay
P1->P2
Rated Current P1
06,0 A
Rated Current P2
06,0A
... back to
Main Menu
HOMA Pump Technology
-
-
17