Библиотека СОК Operating manual HOMA Pump control HSK15 / 25 Ple ase f o llow safet y g u id e line s in ch apt er 2 Version: 03 - 0.06_300704 SW-Version: 1.10c HW-Version: 1.00 Date: 21.10.2004 HSK_operating_manual_English_Ver3.doc...
1 Introduction HOMA HSK is a modular pump control for up to two pumps, which has specifically been designed for use in the wastewater sector. The pump control measures and monitors the level of the medium and depending on the level, starts or stops either one or two pumps. In addition, the HSK continually monitors the built manual motor starters and the pump motor thermo contacts as well as phase sequence and phase drop.
In such case that not all of the information and instructions are found in this operating manual, please ask the manufacturer, HOMA-Pumpenfabrik GmbH (address see page 2). The manufacturer of this device takes no responsibility in case the operating manual is disregarded.
For further details see operation with rechargeable batteries. Attention: If the control unit should not be equipped with a main switch, then this control unit shall be made voltage free before opening of the cover! HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Apart from the above described automatic operation mode, each pump may be manually switched off or on by means of the operating keys or an external toggle switch. For details see Chapter 5.3 Depending on the features, the operation with only one pump is possible as well. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
In addition to the above described fault messages assigned to the pumps, the control unit monitors whether the following faults have occurred: • High water • Phase drop or phase sequence • faults in measuring technique (short circuit or wire breakage in the level sensor cable, inconsistent float switch status HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
LED signals the unit is ready for operation, a red LED indicates faults. The operation of the unit is effected by means of three keys ( , OK, ) (picture 2 below). Optionally, the control unit features additional keys or toggle switches for the 0-Hand-Automatic mode (picture 1 below). HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Using the arrow keys ( ) you can scroll up and down the contents of the menu. Using the OK-key • the alarm buzzer in the Main display can be switched off and the alarms can be reset HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
P1:0M 0,0A float 1 float 2 float 3 1: float switched on (above) 0: float not switched on (below) When using CPS-Version with 4/5 operation keys or manual operation mode switches, the above menus are not present HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
In the menu “Operation mode”, each pump can be changed to the operation modes: AUTOMATIC, manual ON and manual OFF. The change is effected by pressing the OK-key. The current state of operation is then indicated in the menu. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
AUTOMATIC operation mode. System menus and settings Readouts of adjustment values of the control as well as change of operation parameters is effected in 5 submenus: • Level measurement • pump data HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
"contact service" is indicated. In case of this message, the CPS unit is not operable and for security reasons will not start. When self checking is successful, a message is briefly displayed, for example: Mode: 03EE Modem: 0 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
After the measuring method has been selected, it must be confirmed with the OK-key If a 4-20mA level sensor has been selected as measurement method, then after pressing the OK-key, the measuring range of the connected sensor must be additionally entered in cm. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
For example, for a HOMA LLS with measuring range of 2,5m - the value of 0250cm is entered. Important information: If values for the measuring range < 0100cm are entered, then the control inserts the minimum value of 100cm , in case of values >1000cm, the control inserts the maximum value of 1000cm.
When the data is consistent, then the ? sign will not appear and the ↵-sign disappears after entering the last digit. When the control unit operates with float switches, then setpoints are not shown. When the control operates with float switches, the minimum pressure menu is not displayed. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Entering a value of "9999" deactivates the pump rotation function, that is the control starts basically with pump 1 and pump 2 is always the peak load pump. Note: In the case of pump rotation function (1/1) and a value of "9999", pump 2 is never switched on automatically! HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Alarms In this menu behaviour of the control in case of faults is described. The menu has the following structure: Not in case of HSK controls featuring manual 0-Manual-Automatic switch(es) HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Page 20
For example only bits 9...20 which belong to pump1, can be allocated to relay 2. The control unit HSK15 has 2 alarm relays, the control unit HSK25 has 3 alarm relays. In case of HSK15, the menu points for the 3rd alarm relay do not appear.
Page 21
Motor starter has tripped P1FI 0001 RCD (ELCB) has tripped P1DI 0010 Leakage fault P1tmax 0100 Pump run time has been exceeded P1Imin 1000 Pump current too low P1Imax 0001 Pump current too high P1aux1 0010 (reserved) HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
A recommendation for adjusting is given in the above table in the column "auto" ( x = automatic reset; n = no automatic reset; - no recommendation, depending on application). Security Note: The T2-alarm (thermo contact with higher tripping temperature) of controllers used in Ex-endangered areas should not be set to "Auto reset" . HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
In this way fault groups can be assigned to each relay, for example. Relay 1 -> general faults Relay 2 -> Fault Pump 1 Relay 3 -> Fault Pump 2 When the internal buzzer is active, pressing the key once deactivates the buzzer. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
In this menu, general settings of the controller are carried out. The menu has the following structure: Language: Short-Time run every German 999h for 999sec Password: Forced Emptying every 024h Number of Pumps Date Time V0.03 12.03.99 13:38 Time Delay Start: ... back to 0002sec Main Menu HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
If a value of 1000 is entered, then the delay time period (between 0 and 59 seconds) is randomly determined with each new start. The factory default password is 0000 Only in case of a dual pump control HSK25; in case of a single pump control HSK15, this menu does not appear. HSK_operating_manual_English_Ver3.doc...
With a new delivered CPS, therefore, the clock must be set in order to delete the CLOCK-faults. Only for controllers with real-time clock, without real-time clock, this menu does not appear. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
The -key is used to browse backwards in the fault events. To leave the menu, press the OK key. Only in case of controllers with real-time clock, without real-time clock this menu does not appear. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
SW1. Both pumps switch off, when the input is closed. When the input is The operation with three float switches and one pump does not represent a sensible mode of operation. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
The second thermo contact of pump 1 has tripped. The pump is switched off. This fault should confirmed on the controller. This fault is also saved to memory after power loss and is 0 voltage safe. only with HSK25 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Page 31
In case of all faults, both alarm relays switch according to the above mentioned settings, the integrated buzzer sounds (if activated) and the red fault LED will light up. If there is only one flood alarm and the alarm delay time has not elapsed yet, then the red LED flashes. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
There are three (HSK25) or two (HSK15) voltage free relays (SPDT) as alarm outputs available. 10 Standard settings The control is delivered with the following factory standard default settings: Parameter Value Parameter Value Number of pumps Start time delay 3 sec...
Data communication, however, is still possible. When the voltage falls below ca. 9,5V, the control goes in the stand by mode. The following message is displayed: HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Float switch 1 float switch 2 3 x float switch Float switch 1 float switch 2 Float switch 3 (only HSK25) Due to the low currents, it is recommended to use float switches that feature gold flashed contacts. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
The function of the fault memory can best be explained by the following example. Following fault situation has occurred: 10.12.99 13:07 P1 T1 10.12.99 16:10 P1T1, P1MS, HW Then the fault memory shows: 1.10: P1 T1 10.12.99 16:10 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
Max. 230V AC / 24V DC Switching current potential-free alarm relay 5 A max.(AC1) Measuring accuracy hour meter < 0.06% of actual value Working accuracy of real-time clock ±20ppm – 0.04ppm/°C Required external protection of potential-free alarm relay Max. 5A G HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
They are enclosed separately. The layout of the wiring terminals X2 of the control board shows the following picture (HSK25 above; HSK15 below). On the HSK25, terminals 4-20mA+/+ DI1, DI2 are available only as an option. F1 = fuse (protection) of the control.
Attention: In order to comply to the Degree of Protection IP54, the enclosure cover must be closed tight! Not used cable gland holes have to be replaced by a screw cap. 180mm 280mm 380mm d = 7 mm max. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...