Operating manual
HOMA
Pump control
HSK15 / 25
Ple ase f o llow safet y g u id e line s in ch apt er 2
Version: 03 - 0.06_300704
SW-Version: 1.10c
HW-Version: 1.00
Date: 21.10.2004
HSK_operating_manual_English_Ver3.doc
HOMA Pump Technology
-
-
0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HSK15 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Homa HSK15

  • Page 1 Библиотека СОК  Operating manual HOMA Pump control HSK15 / 25 Ple ase f o llow safet y g u id e line s in ch apt er 2 Version: 03 - 0.06_300704 SW-Version: 1.10c HW-Version: 1.00 Date: 21.10.2004 HSK_operating_manual_English_Ver3.doc...
  • Page 2: Table Of Contents

    Rated pump current Communication Alarms 6.4.1 Alarm Auto Reset 6.4.2 Resetting alarms 6.4.3 Alarm relays 1 - 3 6.4.4 Mask Relays 1 - 3 6.4.5 Alarm buzzer 6.4.6 Allowed T1 alarms 6.4.7 High water alarm delay HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 3 12.3 Wiring and connecting diagrams 12.4 Mounting In case of questions and technical problems please contact: HOMA Pumpenfabrik GmbH Industriestrasse 1 D-53819 Neunkirchen - Seelscheid phone +49 - 2247 702 - 0 telefax +49 - 2247 702 - 339 http://www.homa-pumpen.de Stand July 2003 - Technical changes reserved HSK_operating_manual_English_Ver3.doc...
  • Page 4: Introduction

    1 Introduction HOMA HSK is a modular pump control for up to two pumps, which has specifically been designed for use in the wastewater sector. The pump control measures and monitors the level of the medium and depending on the level, starts or stops either one or two pumps. In addition, the HSK continually monitors the built manual motor starters and the pump motor thermo contacts as well as phase sequence and phase drop.
  • Page 5: Application In The Ex - Endangered Areas

    In such case that not all of the information and instructions are found in this operating manual, please ask the manufacturer, HOMA-Pumpenfabrik GmbH (address see page 2). The manufacturer of this device takes no responsibility in case the operating manual is disregarded.
  • Page 6: Load Section

    For further details see operation with rechargeable batteries. Attention: If the control unit should not be equipped with a main switch, then this control unit shall be made voltage free before opening of the cover! HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 7: Motor Protection

    Apart from the above described automatic operation mode, each pump may be manually switched off or on by means of the operating keys or an external toggle switch. For details see Chapter 5.3 Depending on the features, the operation with only one pump is possible as well. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 8: Current Measurement And Ampere Meter Function

    In addition to the above described fault messages assigned to the pumps, the control unit monitors whether the following faults have occurred: • High water • Phase drop or phase sequence • faults in measuring technique (short circuit or wire breakage in the level sensor cable, inconsistent float switch status HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 9: Operation And Displays

    LED signals the unit is ready for operation, a red LED indicates faults. The operation of the unit is effected by means of three keys ( , OK, ) (picture 2 below). Optionally, the control unit features additional keys or toggle switches for the 0-Hand-Automatic mode (picture 1 below). HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 10: Rechargeable Battery Operation

    Using the arrow keys ( ) you can scroll up and down the contents of the menu. Using the OK-key • the alarm buzzer in the Main display can be switched off and the alarms can be reset HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 11: Main Display

    P1:0M 0,0A float 1 float 2 float 3 1: float switched on (above) 0: float not switched on (below) When using CPS-Version with 4/5 operation keys or manual operation mode switches, the above menus are not present HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 12: Pump Operation Mode

    In the menu “Operation mode”, each pump can be changed to the operation modes: AUTOMATIC, manual ON and manual OFF. The change is effected by pressing the OK-key. The current state of operation is then indicated in the menu. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 13: Change Of Operation Mode - Additional Keys

    AUTOMATIC operation mode. System menus and settings Readouts of adjustment values of the control as well as change of operation parameters is effected in 5 submenus: • Level measurement • pump data HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 14: Messages After Starting The System

    "contact service" is indicated. In case of this message, the CPS unit is not operable and for security reasons will not start. When self checking is successful, a message is briefly displayed, for example: Mode: 03EE Modem: 0 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 15: System Menus

    After the measuring method has been selected, it must be confirmed with the OK-key If a 4-20mA level sensor has been selected as measurement method, then after pressing the OK-key, the measuring range of the connected sensor must be additionally entered in cm. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 16: Zero Adjustment

    For example, for a HOMA LLS with measuring range of 2,5m - the value of 0250cm is entered. Important information: If values for the measuring range < 0100cm are entered, then the control inserts the minimum value of 100cm , in case of values >1000cm, the control inserts the maximum value of 1000cm.
  • Page 17: Minimum Pressure

    When the data is consistent, then the ? sign will not appear and the ↵-sign disappears after entering the last digit. When the control unit operates with float switches, then setpoints are not shown. When the control operates with float switches, the minimum pressure menu is not displayed. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 18: Pump Data

    Entering a value of "9999" deactivates the pump rotation function, that is the control starts basically with pump 1 and pump 2 is always the peak load pump. Note: In the case of pump rotation function (1/1) and a value of "9999", pump 2 is never switched on automatically! HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 19: Time Delay Start When Using Dual Pump Operation

    Alarms In this menu behaviour of the control in case of faults is described. The menu has the following structure: Not in case of HSK controls featuring manual 0-Manual-Automatic switch(es) HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 20 For example only bits 9...20 which belong to pump1, can be allocated to relay 2. The control unit HSK15 has 2 alarm relays, the control unit HSK25 has 3 alarm relays. In case of HSK15, the menu points for the 3rd alarm relay do not appear.
  • Page 21 Motor starter has tripped P1FI 0001 RCD (ELCB) has tripped P1DI 0010 Leakage fault P1tmax 0100 Pump run time has been exceeded P1Imin 1000 Pump current too low P1Imax 0001 Pump current too high P1aux1 0010 (reserved) HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 22: Alarm Auto Reset

    A recommendation for adjusting is given in the above table in the column "auto" ( x = automatic reset; n = no automatic reset; - no recommendation, depending on application). Security Note: The T2-alarm (thermo contact with higher tripping temperature) of controllers used in Ex-endangered areas should not be set to "Auto reset" . HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 23: Resetting Alarms

    In this way fault groups can be assigned to each relay, for example. Relay 1 -> general faults Relay 2 -> Fault Pump 1 Relay 3 -> Fault Pump 2 When the internal buzzer is active, pressing the key once deactivates the buzzer. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 24: Alarm Buzzer

    In this menu, general settings of the controller are carried out. The menu has the following structure: Language: Short-Time run every German 999h for 999sec Password: Forced Emptying every 024h Number of Pumps Date Time V0.03 12.03.99 13:38 Time Delay Start: ... back to 0002sec Main Menu HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 25: Language Selection

    If a value of 1000 is entered, then the delay time period (between 0 and 59 seconds) is randomly determined with each new start. The factory default password is 0000 Only in case of a dual pump control HSK25; in case of a single pump control HSK15, this menu does not appear. HSK_operating_manual_English_Ver3.doc...
  • Page 26: Short Time Start

    With a new delivered CPS, therefore, the clock must be set in order to delete the CLOCK-faults. Only for controllers with real-time clock, without real-time clock, this menu does not appear. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 27: System Indications

    The -key is used to browse backwards in the fault events. To leave the menu, press the OK key. Only in case of controllers with real-time clock, without real-time clock this menu does not appear. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 28: Switching Behavior

    Pump 2 Alarm level Cut-in level 2 Cut-in level 1 Cut-out level 2 Cut-out level 1 Switching behavior of the dual pump control Float switch state Pump state 1 Switching behavior in one float switch operation HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 29: Special Functions

    SW1. Both pumps switch off, when the input is closed. When the input is The operation with three float switches and one pump does not represent a sensible mode of operation. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 30: External Alarm

    The second thermo contact of pump 1 has tripped. The pump is switched off. This fault should confirmed on the controller. This fault is also saved to memory after power loss and is 0 voltage safe. only with HSK25 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 31 In case of all faults, both alarm relays switch according to the above mentioned settings, the integrated buzzer sounds (if activated) and the red fault LED will light up. If there is only one flood alarm and the alarm delay time has not elapsed yet, then the red LED flashes. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 32: Standard Settings

    There are three (HSK25) or two (HSK15) voltage free relays (SPDT) as alarm outputs available. 10 Standard settings The control is delivered with the following factory standard default settings: Parameter Value Parameter Value Number of pumps Start time delay 3 sec...
  • Page 33: Pumps With Ptc

    Data communication, however, is still possible. When the voltage falls below ca. 9,5V, the control goes in the stand by mode. The following message is displayed: HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 34: Level Sensor And Float Switch Connection

    Float switch 1 float switch 2 3 x float switch Float switch 1 float switch 2 Float switch 3 (only HSK25) Due to the low currents, it is recommended to use float switches that feature gold flashed contacts. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 35 Wiring diagram examples HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 36: Level Measurement According To The Impact Pressure Method

    The function of the fault memory can best be explained by the following example. Following fault situation has occurred: 10.12.99 13:07 P1 T1 10.12.99 16:10 P1T1, P1MS, HW Then the fault memory shows: 1.10: P1 T1 10.12.99 16:10 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 37: General Technical Data

    Max. 230V AC / 24V DC Switching current potential-free alarm relay 5 A max.(AC1) Measuring accuracy hour meter < 0.06% of actual value Working accuracy of real-time clock ±20ppm – 0.04ppm/°C Required external protection of potential-free alarm relay Max. 5A G HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...
  • Page 38: Wiring And Connecting Diagrams

    They are enclosed separately. The layout of the wiring terminals X2 of the control board shows the following picture (HSK25 above; HSK15 below). On the HSK25, terminals 4-20mA+/+ DI1, DI2 are available only as an option. F1 = fuse (protection) of the control.
  • Page 39: Mounting

    Attention: In order to comply to the Degree of Protection IP54, the enclosure cover must be closed tight! Not used cable gland holes have to be replaced by a screw cap. 180mm 280mm 380mm d = 7 mm max. HSK_operating_manual_English_Ver3.doc HOMA Pump Technology...