System Menus; Level Measurement; Level Measurement Setting - Homa HSK15 Operating Manual

Pump control
Table of Contents

Advertisement

This message is not important for the user and it indicates only the internal configuration for service
purposes. Subsequently the copyright message with the SW-version number is indicated for approx.
1sec. After this, the HSK initiates the start delay time.
6

System menus

6.1

Level measurement

6.2
In the menu "Level measurement", the level measurement method, setpoints, high water levels
as well as the minimum pressure (level measurement with bubbler system) are specified.
6.1.1

Level measurement setting

In this menu, the level measurement method is determined. After pressing the OK-key, the level
measurement method can be selected by means of the
available:
level measurement 4... 20mA interface through level sensor, measuring range adjustable from
0100cm (1meter WC up to 1000cm (10 meters WC)
internal impact pressure sensor (measuring range 0 ... 200 cm WC
1 x float switch
2 x float switches
3 x float switches (only possible with HSK25 in dual pump operation)
After the measuring method has been selected, it must be confirmed with the OK-key
If a 4-20mA level sensor has been selected as measurement method, then after pressing the OK-key,
the measuring range of the connected sensor must be additionally entered in cm.
Level Messurement
4...20mA 0250cm
Automatic
Zero Adjustment
Filter (0-9999)
0000
Minimum Pressure
0005cm
Cut-Out Level
Pump 1: 0030cm
HOMA Pump Technology
Cut-Out Level
Pump 2: 0031cm
Cut-In Level
Pump 1: 0040cm
Cut-In Level
Pump 2: 0061cm
Alarm Level
0091cm
... back to
Main Menu
- or
-key. Following possibilities are
HSK_operating_manual_English_Ver3.doc
-
-
14