FIP FLS F3.00.W Manual page 6

Wireless paddlewheel flow sensor
Table of Contents

Advertisement

• To verify the correct F3.00.W system location, use the following procedures:
- Insert a charged battery into the trasmitter.
- To connect with FLS monitor:
▪ Follow the first calibration procedure on the monitor.
▪ Select the option wireless sensor F3.00.W.
▪ Check the signal strength with the specific function "SIGNAL INTENSITY"
in the calibration menu. The system will return one of the following
intensity level:
LOW > the level of signal is low; any possible external factor can easily
degrade it. It is recommended to reconsider the system location.
MEDIUM > the level of signal is adequate; it is recommended to avoid
upsetting the installation condition (e.g. avoid adding structural elements
as concrete walls between transmitter and receiver)
HIGH > the level of signal is good and safe.
- To connect with PLC:
▪ Check the signal strength:
> Put the JUMPER in the "SIGNAL TEST" position as indicated
in the image below.
> Connect with digital input, as indicated in the section
"POWER WIRING DIAGRAM".
> Set the PLC considering the following correspondence between
the output frequency and the signal intensity:
100Hz > the level of signal is low; any possible external factor
can easily degrade it.
It is recommended to reconsider the system location
200Hz > the level of signal is adequate; it is recommended to avoid
upsetting the installation condition (e.g. avoid adding structural
elements as concrete walls between transmitter and receiver)
300Hz > the level of signal is good and safe.
- Make sure to put the JUMPER in the position "PARK" to make the
system operative. Please refer to image below.
JUMPER IN "SIGNAL
TEST" POSITION
JUMPER IN "PARK"
POSITION