III.4. Anti-boiling protection for the water in the boiler

This protection is applies only to the reboiler priority operation mode.
When the reboiler temperature is set at e.g. 55
temperature in the boiler rises up to 62
temperature), then the controller will turn off the feeder and the fan. If
the temperature in the boiler still rises up to 80
activated. If the temperature is still rising, the alarm will be activated at
the temperature of 85
the reboiler is damaged, the sensor is improperly fastened or the pump is
damaged. However, when the temperature is reducing the controller will
turn on the feeder and the blow-in and at the threshold of 60
operate in the operation mode until the temperature of 62

III.5. Temperature protection

The regulator is equipped with additional protection in the event of
damage to the bimetallic sensor. After exceeding the temperature of
85ºC, the alarm is activated - signalling the following on the display:
"Temperature too high". Despite the damage to the bimetallic sensor,
the controller receives information about the current temperature in the
boiler from the electronic sensor. In the case of exceeding of the alarm
temperature, the fan is turned off and both pumps begin operating
simultaneously, in order to distribute hot water across the house system.

III.6. Protection of fuel container

On the helix of the fuel feeder there is an additional sensor measuring
the temperature. Should it rise significantly (above 70O C), the alarm will
be activated; the feeder is activated for 10 minutes which causes the fuel
to flow to the combustion chamber. This way, the helix sensor protects
the fuel in the container from being ignited.

III.7. Fuel container protection

On the fuel feeder there is an additional temperature measuring
sensor. In the event of its significant increase (above 70O C), the alarm
is activated; the feeder is activated every 10 minutes, which causes
pushing the fuel to the combustion chamber. This way the feeder sensor