Summary - ABB ZX1.5-R Instruction Manual

Gas-insulated medium voltage for railway application

Advertisement

S U M M A R Y

1 Summary

1.1 General
Fundamental features of the panels
Rated voltage up to 27.5 kV
Single or two line metal-clad
Gas insulated
Sealed pressure system for busbar compartment
Sealed pressure system for circuit breaker com
partment
Sensor technology and conventional instrument
transformers for adaptive measuring
Indoor installation
Factory assembled
Type tested
Routine tested
Basic panel variants
Incoming and outgoing feeders
Bus sectionalisers/bus riser panels
Cable side earthing
Panel equipment, variants
Vacuum circuit breaker
Disconnector/earthing switch (three-position
switch) with functions of
-
Busbar connection
-
Disconnection
-
Earthing
Details on the technical design and equipment of
a switchgear, such as
Technical data
Detailed list of equipment fitted
Detailed circuit diagrams, etc
are stated in the order documents.
In addition tothis instruction manual, the following
instruction manuals must be observed:
Insulating gas system
Circuit breaker VD4 X-R
1.2 Standards and specifications
1.2.1 Switchgear production standards and
The ZX1.5-R product comply with the following
standards:
Add GB/T 28428
specifications
1.2.2 Installation and operation
The relevant standards are to be observed during
installation and operation, in particular:
Power installations exceeding AC 1kV,DIN VDE
0101
Operation of electrical installations VDE 0105
Earthing systems for special power
installations with rated voltages above 1 kV,
DIN VDE 0141
The accident prevention regulations issued by
the appropriate professional bodies
The safety guidelines for production materials
The order-related details provided by the
switchgear manufacturer
1.3 Operating conditions
1.3.1 Designed in accordance with DL/T 404,
GB/T 11022, IEC 62271-1, IEC 60628 with
the following limit values:
Ambient temperature
Maximum
Maximum 24 hour average
Minimum
Site altitude
-
≤1000 m above sea level
Ambient air
The ambient air is not to be significantly
contaminated by dust, smoke, corrosive or
flammable gases, or salt.
1.3.2 Special operating conditions
Special operating conditions are to be agreed by
the manufacturer and operator. The manufacturer
is to be consulted in advance about each special
operating condition:
Site altitude above 1000 m
-
The manufacturer's specifications are to be
observed
Increased ambient temperature
-
The current carrying capacity is reduced
-
Additional cooling facilities for heat dissipation
are to be provided
Climate
-
In areas with high humidity or major rapid
temperature changes, condensation inside
the low voltage compartment needs to be
prevented (e.g. by installing electric heaters
in that compartment)
5
+40°C
+35°C
-15°C