D E S I G N A N D F U N C T I O N O F T H E S W I T C H G E A R S Y S T E M A N D I T S E Q U I P M E N T
3.2 Gas system in the panels/switchgear
(Figures 3/7 to 3/11)
A permanently protected climate for the entire
live primary area is ensured by the gas-tight
encapsulation of the panels and their filling
with dry insulating gas.
The circuit breaker compartment (1.0) and
the busbar compartment (2.0) in each panel
are separate gas compartments with their own
filling connectors. The gas compartments in
the individual panels set up side by side are
not connected together
Details on the gas system and gas servicing
of the ZX1.5-R switchgear can be found in
instruction manual HB605/10 Use of SF
insulating gas in ZX Switchgear Insulating
gas system for ZX switchgear
The gas compartments contain drying agent
bags
3.2.1 Monitoring of operating pressure
The rated filling level for insulation in the
individual compartments is monitored by
density sensors
-
Density sensor (1.8) for the circuit breaker
compartment
-
Density sensor (2.3) for the busbar
compartment
Should the pressure in a gas compartment fall
below the alarm level for insulation of that
compartment, this is detected by the switch
bay control unit and displayed on the alarm
side (message text and LEDs)
As an alternative, in versions without switch bay
control unit if pressure drop below the alarm
level for insulation is displayed selectively by
signal lamps
3.2.2 Limitation of the effects of an internal
arc fault
In the unlikely event of an internal arc fault, a
contact in the gas density sensor opens a loop
circuit which runs through all the panels in a busbar
section. On detection of overcurrent at the same
time, the switch bay control unit opens the
corresponding circuit breaker.
Observe the details in the order documents.
3.3 Vacuum circuit breakers, type VD4 X-R
(Figures 3/3, 3/7, 6/3 and separate manual
1YHA000118)
The circuit breaker poles are installed horizontally
in the circuit breaker compartment (1.0). The circuit
breaker operating mechanism (1.2) is located
outside the gas compartment and is therefore
easily accessible. It is connected to the breaker
poles by a gas-tight bushing.
Functions of the vacuum circuit breaker (1.1)
Opening and closing on rated currents
Short-circuit breaking operations
Earthing function in conjunction with
three-position switch (2.1)
The earthing function of the three-position switch
prepares de-energized for the connection to earth.
Earthing itself is performed by the circuit breaker.
This integration of functions is advantageous, as
a circuit breaker is of higher quality in the earthing
function than any other earthing switch.
3.4 Disconnector/earthing switch, type UX2TE-R
(Three-position switch) (Figures 3/7, 6/2,
6/4)
6
The ZX1.5-R panels are fitted with specially
designed three-position disconnectors and
earthing switches (2.1) (-Q1/-Q5). These switches
are motor-operated rod-type switches whose live
switching components are located in busbar
compartment (2.0) (insulating gas compartment),
while the operating mechanism block is easily
accessible from the control cabinet (4.0).
The operating mechanism block consists of the
following functional groups:
The drive motor
Position indicators with integrated LEDs for
position indication or the combination
microswitches and auxiliary contacts
Mechanical position indicators
Emergency manual operating drive
Optional: mechanical interlocking for emergency
manual operation
The three-position switch performs the
functions of:
Connecting
Disconnecting and
Earthing
The three switch positions are unequivocally
specified by the operating mechanism. The switch
has its disconnecting position at the centre. In the
limit positions, disconnector ON and earthing
switch ON, the moving contact (sliding part)
driven by an insulating spindle, reaches the
isolating contacts, which are fitted with one or
two contact rings respectively.
3.5 High voltage connections
(Figures 3/2, 3/7, 5/8, 6/6)
Cable plug connector systems
High voltage plastic insulated cable with internal
cone cable plug connector system and sockets
to EN 50181
Plug systems: size 3.
11