set> SD CARD INSTALL
VAIE 5500
Setting of zone level during emergencies
The standard alert and evacuation messages and the broadcast chime are
stored at the factory on the SD card mounted on the CPU circuit.
In order to customise the system, it is possible, however, to add to and/or up-
date these fi les. To do so, it is necessary to:
-
Place the main thermal-magnetic circuit breaker upstream from the system
in the OFF position: the VAIE 5500 enters the stand-by mode, exploiting
the power supply from the batteries.
-
Open the front door of the VAIE 5500 by unscrewing the two fi xing screws:
the amplifi ers will automatically switch off.
-
On the display, press the Turn off SD key: the red LED associated with
the card extinguishes. At this point it is possible to extract the SD from the
VAIE 5500.
-
Programme the card with the new audio fi les (max. 20).
Following are the requisites of the fi les, which have to be copied into the
root directory of the SD card:
• Format: *.WAV
• Resolution: 16 bit / mono
• Sampling frequency: 48 kHz
• Filename: max 16 characters (including the .wav extension).
-
UOnce the fi les have been copied onto the SD card, fi t it back onto the
CPU circuit and, on the display, press the Turn on SD key. Check that the
red LED lights up again.
-
Close the front door of the VAIE 5500, tightening the screws fi rmly back
into place.
-
Return the main thermal-magnetic circuit breaker to its ON position.
The SD card is now mounted correctly and the menu on the display shows a list
up-dated with the new audio fi les, which can be browsed using the Up/Dn keys.
To set the new EVACUATION message (EVAC):
Select the desired fi le and press the Set evac key.
To set the new ALERT message:
Select the desired fi le and press the Set alert key.
To set the new broadcast CHIME:
Select the desired fi le and press the Set chime key.
The names of the fi les set appear as a reminder at the bottom of the screen,
together with the type of use.
To return to the CONFIGURATION menu press Escape.