Fbt LIGHT Instructions For Use Manual page 33

Wall-mounted voice evacuation system 500w / 2 zones
Table of Contents

Advertisement

Label
Application
Control input
Controlled Input contacts
Output
Relay output
Charger
Battery charger
VAIE 5500
See panel
2 AMP (Pmax = 250W)
Capacity Duration without mains supply
18 Ah
24 h + 30 min*
26 Ah
35 h + 30 min
33 Ah
44 h + 30 min
40 Ah
72 h + 30 min
33
Notes
Panel for confi guring the controlled
inputs.
To go from one input to another
(from 1 to 7), press Next or Prev.
Press Mode to select one of the
following modes:
- Message input > Edit zone
Setting of the messages for the
zones (E = evac, A = alert,
N = none)
- Not active input
- Reset input
Press Control to enable or disable
control over the concerned input.
Press Logic to set the logic
typology attributed to the
concerned input, choosing
between:
- Positive (active high)
- Negative (active low)
To leave the screen, press
'Escape'.
Panel for confi guring the relay
output.
Activate or de-activate (On/Off) the
type of event to be associated with
the output in question by pressing
the appropriate buttons.
To leave the screen, press
'Escape'.
Battery confi guration panel.
By pressing 'Change' it is possible
to set:
- The capacity of the battery
(choose between 18, 26, 33
or 40 Ah).
- 'Energy save' mode enabled
disabled. This enables the
batteries to remain in the
energy saving mode when
there is no mains power.
*
According to UNI ISO 7240-19
point 5.15.3 requirements:
24 h standby plus 30 minutes in vocal
alarm condition.
EN