Siemens SIMATIC C7-635 Manual page 81

Table of Contents

Advertisement

Interference Suppression, Error Limits
Interference voltage suppression for f = n x (f1+/– 1 %),
(f1 = interference frequency), n = 1, 2
Common mode interference
(VCM < 8.0 V)
Feedback interference (peak
value of the interference <
rated value of the input range)
Crosstalk between the inputs
Operational error limits (throughout temperature range, relative to input range)
Voltage/current
Resistance
Basic error limits (operational limit at 25°C, relative to input range)
Voltage/current
Resistance
Temperature error (related to input
range)
Linearity error (related to input
range)
Accuracy of reproducibility (in
steady state at 25 ° C, relative to
input range)
Status, Interrupts, Diagnostics
Interrupts
Diagnostic functions
Siemens Controls
C7-635 Control System
A5E00155581-04
> 40 dB
> 30 dB
> 50 dB
< 1 %
< 5%
< 0.7%
< 3%
+/– 0.006 %/K
+/– 0.06%
+/–0.06%
No interrupts when operated as standard I/O
When using the technological functions,
see CPU 31xC Technological Functions manual
No diagnostics when operated as standard I/O
When using the technological functions,
see CPU 31x Technological Functions manual