Residential Pendent and
Recessed Pendent Sprinklers
Star Galaxy™ SG-R, K=4.3
GENERAL DESCRIPTION
The Star Galaxy SG-R Residential Pendent and Re-
cessed Pendent Sprinklers are decorative glass bulb
sprinklers designed for use in residential occupancies
such as homes, apartments, dormitories, and hotels.
They are to be used in wet pipe residential sprinkler sys-
tems for one- and two-family dwellings and mobile homes
per NFPA 13D; wet pipe residential sprinkler systems for
residential occupancies up to and including four stories in
height per NFPA 13R; or, wet pipe sprinkler systems for
the residential portions of any occupancy per NFPA 13.
The Star Galaxy has a 4.3 (61,9) K-factor which provides
very low design flow rates at reduced residual pressures,
enabling smaller pipe sizes and water supply require-
ments.
The recessed version of the Star Galaxy SG-R using a
#2084 Recessed Escutcheon provides 1/4 inch (6,4 mm)
of recessed adjustment or up to 1/2 inch (12,7 mm) of to-
tal adjustment from the flush pendent position. The re-
cessed adjustment substantially reduces the accuracy to
which the length of fixed pipe drops to the sprinklers must
be cut.
The Star Galaxy SG-R has been designed with heat sen-
sitivity and water distribution characteristics proven to
help in the control of residential fires to improve the
chance for occupants to escape or be evacuated. How-
ever, residential fire sprinkler systems are not a substitute
for intelligent fire safety awareness or fire safety construc-
tion required by building codes.
WARNINGS
The Star Galaxy SG-R Residential Pendent and Re-
cessed Pendent Sprinklers described herein must be
installed and maintained in compliance with this
document, as well as with the applicable standards of
the National Fire Protection Association, in addition
to the standards of any other authorities having juris-
diction. Failure to do so may impair the integrity of
these devices.
Because of the above cited stipulations and the var-
ied nature of residential type architecture, there will
be some compartment designs which cannot be fully
sprinklered in accordance with the recommendations
of NFPA 13, 13D, or 13R. In the event of this condi-
tion, consult the authorities having jurisdiction for
guidance and approval.
It is the responsibility of the installing contractor to
provide a copy of this document to the owner or their
representative, and in turn, it is the obligation of the
TYCO FIRE PRODUCTS
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500
SIN S2287
#2084 Recessed Escutcheon
owner to provide a copy of this document to a suc-
ceeding owner.
The owner is responsible for maintaining their fire
protection system and devices in proper operating
condition. The installing contractor or sprinkler manu-
facturer should be contacted relative to any ques-
tions.
OPERATION
The glass bulb contains a fluid which expands when ex-
posed to heat. When the rated temperature is reached,
the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. NYC Accepted (MEA 395-91-M).
(The approvals apply only to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
1/2
K = 4.3 GPM/psi
(61,9 LPM/bar
Temperature Rating
155°F/68°C
Finishes
Sprinkler: White Polyester, Chrome Plated, Natural Brass
Recessed Escutcheon: White Coated or Chrome Plated
(Colors other than white available on request.)
Physical Characteristics (Ref. Figure 1)
The Star Galaxy SG-R utilizes a dezincification resistant
(DZR) bronze frame, and a 3 mm diameter glass bulb.
The two-piece button assembly is brass and copper. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
with a Teflon V gasket. The compression screw is bronze,
and the deflector is brass.
#2287 Shown With
1/2
)
1-3.2.10
7-02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Star Galaxy SG-R and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product Star Galaxy SG-R

  • Page 1 The recessed version of the Star Galaxy SG-R using a #2084 Recessed Escutcheon provides 1/4 inch (6,4 mm) TECHNICAL DATA of recessed adjustment or up to 1/2 inch (12,7 mm) of to- tal adjustment from the flush pendent position.
  • Page 2: Design Criteria

    Figure 2. Hydraulic Design Criteria. The minimum required flow The Star Galaxy SG-R must NOT be used above or be- rates for residential applications are given in Table A as a low open-gridded type suspended ceilings; beneath sof- function of the maximum allowable coverage areas.
  • Page 3: Installation

    PLATE FITTING 1/8" (3.2 mm) INSTALLATION MOUNTING SURFACE The Star Galaxy SG-R must be installed in accordance with the following instructions: 1-1/4" (31.8 mm) CLOSURE SG-R 1" (25.4 mm) NOTES Do not install any bulb type sprinkler if the bulb is FIGURE 2 cracked or there is a loss of liquid from the bulb.
  • Page 4 Page 4 STAR SPRINKLER 1-3.2.10 FIGURE 5 PLAN VIEW ILLUSTRATIONS OF SPRINKLER-TO-WALL AND SPRINKLER-TO-SPRINKLER POSITIONING...
  • Page 5 1-3.2.10 STAR SPRINKLER Page 5 FIGURE 6 MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN TWO SPRINKLERS LOCATED ON THE SAME ELEVATION ON OPPOSING SLOPED CEILINGS FIGURE 7 MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER DEFLECTOR AND THE BOTTOM OF NON-CONTINUOUS CEILING OBSTRUCTIONS...
  • Page 6 Page 6 STAR SPRINKLER 1-3.2.10 FIGURE 8 MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LOCATED ON A LEVEL CEILING AND AN INTERSECTING SLOPED CEILING FIGURE 9 MINIMUM REQUIRED SLANT DISTANCE BETWEEN A LEVEL CEILING AND A SPRINKLER LOCATED ON AN INTERSECTING SLOPED CEILING...
  • Page 7: Care And Maintenance

    (i.e., dusting) Service. brush attachment. The Star Galaxy SG-R must only be replaced with pen- Exercise suitable safety precautions in the use and dent sprinklers which are listed for residential fire protec- storage of highly flammable materials. The rapid rate...
  • Page 8: Limited Warranty

    Products manufactured by Tyco Fire Products are war- Please Specify: ranted solely to the original Buyer for ten (10) years 1 Star Galaxy SG-R, 4.3 K-Factor, Residential against defects in material and workmanship when paid Pendent Sprinkler (#2287) for and properly installed and maintained under normal 2.

Table of Contents